beautypg.com

Technical data, 5 differential pressure regulators – KROHNE DK 32 Purge EN User Manual

Page 29

background image

TECHNICAL DATA

7

29

DK32

www.krohne.com

04/2011 - 4000898801 MA DK32 Air purge set R02 en

7.5 Differential pressure regulators

Differential pressure regulators are used (DK32 and DK37 only) to help maintain constant flow
rates in the case of fluctuating inlet or outlet pressures. Minimum pressure levels are required
to permit operation of the regulators (see Regulator characteristics).

Differential pressure regulators are not pressure reducing valves!

1 Inlet pressure regulators, types RE, NRE
The regulators maintain a constant flow rate at variable inlet pressure and constant outlet
pressure.

2 Outlet pressure regulators types RA, NRA
The regulators maintain a constant flow rate at constant inlet pressure and variable outlet
pressure.
In order to function, there must be pressure difference between the inlet pressure and
the outlet pressure. The inlet pressure p1 must always be greater than the outlet pressure p2.

Regulator characteristics

Example: Inlet pressure regulator RE-1000:

Current flow rate:

1000l/h air

Constant outlet pressure

p2:

1.013 bar abs.

With a variable inlet pressure greater than 0.5 bar the flow rate in the device is constant.

Example: Outlet pressure regulator NRA-

800

Current flow rate:

800l/h air

Constant inlet pressure:

6 bar

With a variable outlet pressure of 0...5.5 bar the flowrate in the device remains constant.

1 Inlet pressure regulators, types RE and
NRE

2 Outlet pressure regulators, types RA and
NRA

MA_DK32_Purge_R02_en_898801_PRT.book Page 29 Wednesday, April 6, 2011 3:01 PM