beautypg.com

Profibus settings, 4 menu d, service – KROHNE MFC 300 Profibus User Manual

Page 38

background image

5

PROFIBUS SETTINGS

38

MFC 300

www.krohne.com

07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en

5.4 Menu D, Service

This menu is protected. You will need to use the service password to gain access.

No.

Function

Settings / descriptions

D2

In this menu all functions related to different data sets can be found.

D2.2

Service Parameters

D2.2.1

Cold Start

Resetting of the signal converter can be done here but all changes up to this

point are automatically stored and cannot be discarded.

Select: no (terminates the function) / yes (performs the reset and leaves the

setting mode)

D2.2.2

Save Factory Data

Copies the actual data into the factory setting; this overwrites the factory

settings done during calibration!

Query: save settings? (cannot be undone)

Select: break (exit function without saving) / factory settings (saves the

settings as factory settings)

Query: continue copy? (cannot be undone)

Select: no (exit function without saving) / yes (copy current settings to the

selected storage location)

D2.2.4

Identification No.

Sets different device modes for the cyclic communication of the PROFIBUS

interface.

Select: signal converter (the normal settings incl. all manufacturer specific

parameters are supported) / profile (uses only the profile defined functions,

no extras, only profile specific parameters are supported) / MFC050/051

(compatibility mode)

D2.2.5

PB Cold Start

Initiates a PROFIBUS cold start.

During a PROFIBUS cold start nearly all parameter values of the whole

device will be set to their default values (Exceptions are the PROFIBUS

address and the identification No.). The cold start will be carried out without

disconnecting an already established connection to a PROFIBUS master

system.

Query: reset? (to default values) = cold start begins

Select: no (terminates the function) / yes (PROFIBUS cold start will be

carried out at once; the setting mode is terminated)

D2.2.7

Diag. extension h

h = history

Delete the stored history.

Query: reset? = reset history to 0)

Select: no (no change) / yes (all saved data are deleted)