PROFIBUS PA
3
19
MFC 300
www.krohne.com
07/2014 - 4001086802 - AD MFC 300 PROFIBUS R02 en
3.5.3 Manufacturer specific GSD files: KR014511.GSD and YP014511.GSD
The KR014511.GSD file is for use with the standard DP/PA coupler and the YP014511.GSD file is
for use with the transparent DP/PA coupler SK2/SK3 of Pepperl & Fuchs (up to 12 MBaud on the
DP segment).
It should be noted that both GSD files support device functionality as described below:
• AI: Analog Input Function Block
• FB: Function Block
There are separate settings to select the units for local display and PROFIBUS. Modifications of
the units of the display will have no effect on the data transferred via PROFIBUS.
A master class 2 tool is required to modify the units for PROFIBUS transfer.
INFORMATION!
For devices with MBP interface there are always two types of GSD files in our GSD compilation:
•
One standard GSD file for a standard DP/PA segment coupler with file name: "KR0
…
.GSD"
•
One special GSD file specific for the segment coupler SK2/SK3 of Pepperl & Fuchs with file
name: "YP0
…
.GSD"
Block
number
Default configuration
Function block output: value and
status
KR014511.GSD
YP014511.GSD
Ident-No. 4511
Default
unit
1
Mass Flow
AI-FB
kg/s
2
Density
AI-FB
kg/m
3
3
Medium Temperature
AI-FB
K
4
Mass Totaliser
Totaliser-FB
kg
5
Volume Totaliser
Totaliser-FB
m
3
6
Mass Totaliser
Totaliser-FB
kg
7
Volume Flow
AI-FB
m
3
/h
8
Concentration 1
AI-FB
%
9
Concentration 2
AI-FB
%
10
Concentration Mass Flow 1
AI-FB
kg/s
11
Concentration Mass Flow 2
AI-FB
kg/s