Condensed instructions IFC 020

π

4

π

4

4.2 Table of settable functions

Fct.

Text

Description and settings

1.00

OPERATION

Operations menu

1.01

FULL SCALE

Full-scale range for flowrate Q

100%

Select unit
m

3

/hr

Liter/Sec

US.Gal/min

user unit, factory set is “Liter/hr” or “US MGal/day” (see Fct. 3.05)

Press

key to transfer to number setting.

Setting ranges
The ranges are dependent on the meter size (DN) and the flow

velocity (v): Q

min

= DN

2

x v

min

Q

max

= DN

2

x v

max

Nom. dia./meter size

v

min

= 0,3 m/s (1 ft/s) v

max

= 12 m/s (40 ft/s)

DN 2.5–1000 /

1

/

10

”–40”:

0.0053 –

0

33 900 m

3

/hr

0.0237 –

152 000 US.Gal/min

Press

key to return to Fct. 1.01 FULL SCALE.

VALUE P

Pulse value (Fct. 1.06 “VALUE P”) has been changed.

With the “old” pulse values the output frequency (F)
would have been exceeded or not reached.

P

min

= F

min

/ Q

100%

P

max

= F

max

/ Q

100%

Check new values!

1.02

TIMECONST.

Time constant
Select:

ALL (applies to display and all outputs)
ONLY I+S (only display, current and status outputs)

Press

key to transfer to number setting.

Range:

0.2 – 99.9 Sec

Press

key to return to Fct. 1.02 TIMECONST.

1.03

L.F.CUTOFF

Low-flow cutoff (SMU)
OFF (fixed values: ON = 0.1% / OFF = 0.2%

at 100Hz and 1000Hz, see Fct. 106, 1% resp. 2%)

PERCENT (variable values)

ON OFF
1 – 19% 2 – 20%

Press

key to transfer to number setting.

Note: Cutoff “off” value must be greater than cutoff “on” value.
Press

key to return to Fct. 1.03 L.F. CUTOFF.

1.04

DISPLAY

Display functions

DISP.FLOW

Select flow display
NO DISP. user unit, factory set is “Liter/hr” or “US MGal/day (see Fct. 3.05)
m3/hr

PERCENT

Liter/Sec

BARGRAPH (value and bargraph display in %)

US.Gal/min

Press

key to transfer to subfunction “DISP. TOTAL.”.

DISP.TOTAL.

Select totalizer display
NO DISP. (totalizer switched on but not displayed)
OFF (totalizer switched off)

+TOTAL

−TOTAL

±TOTAL

SUM (

Σ)

ALL (single totalizer or all)
Press

key to transfer to display unit

m3

Liter

US.Gal

user unit, factory set is “Liter” or “US MGal” (see Fct. 3.05).

Press

key to transfer to format setting.

Format setting
• Auto (exponent notation)
# . #######

##### . ###

## . ######

###### . ##

### . #####

####### . #

#### . ####

########

Press

key to transfer to subfunction “DISP.MSG”.

DISP.MSG.

Additional messages required in measuring mode?
NO

YES (cyclic change with displays of measured values)

Press

key to return to Fct. 1.04 DISPLAY.