Condensed instructions IFC 020

2/1

• All operating data and functions can be set: Operation

see section 4 and 5.7 function 1.06 and 1.07.

• The pulse and status outputs can be operated in the active or passive mode.

Active mode:

The current output is the internal voltage source,

connection of electronic totalizers (EC)

Passive mode:

External DC or AC voltage source required, connection of electronic (EC)

or electromechanical (EMC) totalizers

• Digital pulse division, interpulse period is non-uniform. Therefore, if frequency meters or

cycle counters are connected, allow for minimum counting interval:

gate time, counter

1000

P

100%

[ Hz]

Connection diagrams see Sect. 2.4: diagrams - pulse output

diagrams - status output

2.1 Current output I

The current output is galvanically isolated from all input and output circuits.

Factory-set data and functions can be noted down in Sect. 5.16.

Please also refer to Sect. 3.2 “Factory settings”.

Typical current output

All operating data and functions can be set: Operation see section 4 and 5.6 fuction 1.05.

The current output can also be used as an internal voltage source for the outputs.

U

int

= 15 V DC I = 23 mA when operated without receiver instruments at the current output

I = 3 mA when operated with receiver instruments at the current output

Connection diagrams, see Sect. 2.4: diagrams

For Connection and operation with HART

®

-interface see section 6.1.

I+ approx. 15 V DC positive

voltage of current output

I current sink

I

⊥ chassis ground, current output

2 Electrical connection of outputs and inputs

2.2 Pulse output P and status output S

• The pulse and status outputs are galvanically isolated from the current output and all input circuits.

• Factory-set data and functions can be noted down in Sect. 5.16.

Please also refer to Sect. 3.2 “Factory settings”.

• Typical pulse and status outputs

S status output

P

⊥ chassis ground

P pulse output