beautypg.com

KROHNE IFC 020 Short EN User Manual

Page 12

background image

Condensed instructions IFC 020

2/3

2.4 Input / output connection diagrams

Terminal identification

IFC 020 E separated, 19” plug-in unit, connection

IFC 020 F separated, field housing

IFC 020 K compact

For connection and operation of the HART® interface,
see section 6.1. Burden (load) at HART® operation ranges
between min. 250

and max. 500

.

E: X2

F

K

I

Current output C

Control input (IFC 020 E only)

P Pulse output

S Status output RS 485 Interface

1

2

I

= 0/4 - 20 mA

U

ext

15...20 V DC 20...32 VDC

R

i

0...500

Ω 250...750 Ω

U

ext

≤ 15 V DC

I

= 0/4 - 20 mA

R

i

≤ 500 Ω

Current output

I

active

Current output

I

passive

Active mode

The current output supplies the power for

operation of the outputs and inputs.

Passive mode

External power source required for operation of

the outputs and inputs.

3

4

Pulse output P

passive

for electronic (EC) or

electromechanical (EMC) totalizers

U

ext

≤ 32 V DC/≤ 24 V AC

I

max

≤ 150 mA

(incl. status output S)

U

int

≤ 15 V DC from current output

Operation with current output:
I

max

≤ 3 mA

Operation without current output:
I

max

≤ 23 mA

R

15 V

I

max

Pulse output P

active

(and current output I

active

)

for electronic (EC) totalizers

with and without current output I

Totalizer

- electronic (EC)

- electromechanical (EMC)

Milliammeter

0 or 4-20mA and others

Key, N/O contact

External voltage source (U

ext

),

DC or AC voltage,

connection polarity arbitrary

DC voltage,

external power source (U

ext

),

note connection polarity

U

ext

U

ext

I

max

+