1 Set the function switch to position [5] (Decimal Point).
2 By pushing the [+/-] keys, you move the decimal point.
3 Save the value by pushing both keys simultaneously.

l

Set the function switch to position [ 1 ] (relay 1 on). For the

given example, select the value 90.0 (90.0 %) with the [ +/-

] keys. The internal relay 1 then switches on when this

value is reached. Save the value by pushing the two keys

simultaneously.

l

Set the function switch to position [ 2] (relay 1 off). Select

the value 10.0 (10.0 %) with the [ +/-] keys. The internal

relay 1 then switches off when the value falls below this

value. The respective relay control lamp lights when the

relay is energized. If the switching points are too close

together (<0.1 %), the appropriate LED flashes. The relay

takes on the safe condition. In mode "OPERATE " an error

message is outputted on the display.

l

If you want to control additional relays, proceed in the same

way, as with relay 1. The switch positions for setting the

respective relays are stated in the list of the function switch

under "Setup procedure".

Note:

If you want to change the mode (i.e. the switching function of

the relays), you have to exchange the On and Off values.

Relay

22

SU 600 Ex - 4 ... 20 mA signal conditioning

Setup with the integrated indicating and adjustment unit