The max. filling volume is 2650 l, the min. filling volume 50 l

l

The level sensor in the vessel is a pressure transmitter

(passive), outputting a standardised 4 … 20 mA signal

l

For further processing, an additional 4 … 20 mA output

signal is required

l

The full and empty adjustment was carried out directly in

the sensor. The following values are outputted:

- max. volume (display max.) 20 mA = 2650 l

- min. volume (display min.) 4 mA = 50 l

l

Relay 1 should switch on an emptying pump at a level of

90 % and switch off the pump at a level of 10 %

1 Select the following functions with the rotary switch.
2 Push one of the two [+/-] adjustment keys, the digital

indication flashes (if the rotary switch is set to "OPERATE",

the [+/-] keys are inoperable).

3 Adjust the requested value with the [+/-] keys. If you hold

the key pushed, the digital indication changes the value

more quickly.

4 Save your settings by pushing the [+/-] keys simultane-

ously.

à

Set the function switch to position [8]. Select with the [+/-]

keys the measured value output 4 … 20 mA or 0 … 20 mA.

For this example, choose 4 – 20.

The displayed numbers have the following meanings:

l

0 – 20 = 0 … 20 mA

l

4 – 20 = 4 … 20 mA

à

Save the value by pushing the [+/-] keys simultaneously.

To scale the indication of SU 600 Ex, the filling volumes for 0 %

and 100 %. The vessel does not have to be filled or emptied.

1 Set the function switch to position [7] (display min.).
2 Set the value to 50 via the [+/-] keys.
3 Save the value by pushing both keys simultaneously.

1 Set the function switch to position [6] (display max.).
2 Set the value to 2650 via the [+/-] keys.
3 Save the value by pushing both keys simultaneously.

Because the range of the example vessel is between 50 l to

2650 l, you will need all four positions of the digital indication.

General procedure

Current output

Scaled indication at 0 %

Scaled indication at 100 %

Decimal point

SU 600 Ex - 4 ... 20 mA signal conditioning