Information:

Via the slide switch on the rear of the instrument you can

switch over between active and passive operation of the

measuring data input:

l

In active mode,SU 600 Ex provides the power for the

connected sensors. Power supply and measurement data

are transmitted over the same two-wire cable. This mode is

provided for connection of transmitters without separate

power supply (sensors in two-wire version).

l

In passive mode, the sensors are not powered - only the

measured value is transmitted. This input is for transmitters

with their own separate power supply (sensors in four-wire

version). Furthermore,SU 600 Ex can be connected to an

existing circuit like a standard current meter.

The position of the slide switch also influences the precondi-

tions for Ex implementation. Take note of the type approval

certificate or the conformity certificate ofSU 600 Ex.

14

SU 600 Ex - 4 ... 20 mA signal conditioning