KROHNE SU 600 Ex EN User Manual
Page 19
2
1
3
off (on)
on (off)
o n
o n
o f f
o f f
t
L E D
1
Level
2
Mode overfill protection
3
Mode dry run protection
Scaling is the conversion of the measured value into a certain
parameter or measuring unit. Instead of the percentage value,
the volume can be displayed, e.g. in l. Indicating values
between max. -9999 and +9999 are possible.
à
First of all, determine the max. indicating range and the
number of decimal places after the decimal point -- max.
four decimal places can be displayed. Select position [ 5 ]
of the function switch, place the decimal point in the
required position and save your settings.
à
Now select position [6] or [7] on the function switch, enter
the requested values for 100 % or 0 % and save your
settings.
To suppress fluctuation in the measured value display, e.g.
caused by an agitated product surface, an integration time can
be set. This time can be between 0 and 250 seconds. Keep in
mind that this setting will increase the reaction time of the
measurement, and that the reaction to quick changes of the
measured value will be delayed. In general, a time of a few
seconds is sufficient to smooth the measured value display.
Scaling
Damping
SU 600 Ex - 4 ... 20 mA signal conditioning
19
Setup with the integrated indicating and adjustment unit
30653
-EN