ELECTRICAL CONNECTIONS

12

PTD 600

www.krohne.com

03/2012 - 4001946801 - MA PTD 600 R01 en

4.3 Electrical connection diagram

DANGER!

Check polarity and use shielded cables.

The transmitter housing and shield must be grounded.

Place the shielding on the control side to ground across a large area to ensure the best
possible protection against electromagnetic interference.
For field housing versions, place the shield evenly on the contact surface of the cable
feedthrough.

Avoid potential differences between the transmitter housing and the control if at all possible.
To comply fully with PELV requirements in accordance with EN 60204-1 §6.4.1, connect 0 V
(ground) to a point in the system with protective earth.

Figure 4-3: Electrical connection diagram

a: pressure transmitter
b: power supply / measuring unit

1 +V

S

(supply voltage)

2 I

Out

/GND (current output)

3 R

Load

4 Ground
5 Measurement
6 Operating voltage