System Operation (cont’d)

Sending Messages to a Pager

The FOCUS 200 PLUS system can transmit messages to up to 8 paging
services (typically one for each group). The types of messages are divided
into 4 categories: System Troubles, Point Troubles, Alarms and Open/Closes.
Additionally, the system can be programmed to attempt to dial the paging
service either once or twice (the default is twice).

The format of the pager message is as follows:

EEE GGG UUUU

EEE = Event Code

GGG = Group Number (001-008)

UUUU = User Number (for open/closes) or Point Number.

The possible event codes are:

111 = Fire Alarm

222 = Hold-up or Hostage Alarm

333 = Burglary Alarm

400 = Group failed to Turn OFF

444 = Group was Turned OFF

500 = Group Failed to Turn ON

555 = Point or System Trouble

777 = Group was Turned ON

911 = Personal Emergency (Medical

Alarm)

The following is an example of a pager message:

444 001 0025