beautypg.com

Electrical connections – KROHNE OPTIFLUX 2000-4000-5000-6000-7300-IFC 300 Ex EN User Manual

Page 36

background image

4

ELECTRICAL CONNECTIONS

36

OPTIFLUX

www.krohne.com

07/2010 - 7309482600 - AD EX IFC 300 R06 en

Up to a maximum of 4 intrinsically safe (Ex ia) in-/outputs are possible. All intrinsically safe
circuits are galvanically insulated with respect to earth and each other. To avoid summation of
voltages and current, the wiring of these “Ex ia”-circuits must be sufficiently separated, e.g. in
accordance with the requirements of standard EN 60079-14, clause 12.2.
The “Ex ia” signal in-/outputs may only be connected to other “Ex ia” or “Ex ib” approved devices
(e.g. intrinsically safe isolation amplifiers), even if such devices are installed in a non-hazardous
location !
Connection to non-“Ex i” devices cancels the “Ex ia” properties of the flowmeter.

Terminals L and N (or L+ and L-) for connection of the mains supply are not available with type of
protection “intrinsic safety”. To achieve the necessary separation distances according to EN
60079-11 between the non-”Ex i” and “Ex i” circuits, the mains terminals are provided with a
semi-circular protection cover with a “snap-in” lock. This cover MUST be closed before
establishing the power supply to the converter.

INFORMATION!
For converters with an

Ex e

terminal compartment, the compartment can be opened in an

energized state for short periods of time, to access the intrinsically safe terminals for possible
checks. However, the semi-circular insulation cover over the non-intrinsically safe mains supply
terminals L and N (or L+ and L-) MUST be kept closed.

INFORMATION!
More detailed information about the connections can be found in the handbook of the converter.