2

TEMPERATURE LIMITS

20

OPTIFLUX

www.krohne.com

07/2010 - 7309482600 - AD EX IFC 300 R06 en

2.1.2 Field versions

• In general the OPTIFLUX 2000 F / 4000 F flow sensors are suitable for an ambient

temperature range of -40...+60°C.

• For dust hazardous areas the maximum surface temperature is equal to the process

temperature T

p

with a minimum of 85°C.

• The minimum process temperature is -40°C.
• The maximum process temperature Tp is dependent on the required temperature class

T6/T5...T3, the diameter and the maximum ambient temperature T

a

. The temperature range

is often limited further by the liner type used (refer to the Quick Start).

DN10...20 ("me")

DN25...150 ("d")

DN200...300 ("qe")

Temperature class

Max. process temperature Tp [°C]

T

a

≤ 40°C

40 < T

a

≤ 50°C

50 < T

a

≤ 60°C

T6

75

70

70

T5

95

90

75

T4

130

115

75

T3

150

115

75

Temperature class

Max. process temperature Tp [°C]

T

a

≤ 40°C

40 < T

a

≤ 50°C

50 < T

a

≤ 60°C

T6

70

70

70

T5

85

85

85

T4

120

120

120

T3

180

180

180

Use heat resistant

cables for T

p

above:

1

Not needed

155

105

1 Cables must withstand a continuous operating temperature of 85°C.

Temperature class

Max. process temperature Tp [°C]

T

a

≤ 40°C

40 < T

a

≤ 50°C

50 < T

a

≤ 60°C

T6

75

70

70

T5

95

90

75

T4

130

115

75

T3

150

115

75