III — SPECIFICATIONS

Specifications for each model are listed below.

INPUT CHARACTERISTICS:

INPUT VOLTAGE:

Nominal 24V d-c, Operating Range: 12V** to 35V d-c

** Consult factory for operation below 24V nominal.

NUMBER OF INPUTS:

Two (2): A and B

INPUT AND OUTPUT CURRENT: Per input:

30A max.

NOTE: For parallel operation of both circuits

maximum output current of each circuit

must not exceed 30A.

VOLTAGE DROP: Input to Output

0.5V d-c typ.

REVERSE OUTPUT VOLTAGE:

45V d-c max

ALARM, INPUT VOLTAGE (UNDERVOLTAGE):

Indicators (A and B): UV LED

— Relays (A and B): isolated contacts rated at

28V d-c/1A or 115V a-c/0.5A

— Range: See Figure 5 and Table 2.

— Factory preset: See Figure 5 and Table 2.

— Hysteresis: See Figure 5 and Table 2.

ALARM, INPUT VOLTAGE (OVERVOLTAGE):

— Indicators (A and B) OV LED

— Relays (A and B): isolated contacts rated at

28V d-c/1A or 115V a-c/0.5A

— Range: See Figure 5 and Table 2.

— Hysteresis: See Figure 5 and Table 2.

— Factory preset: See Figure 5 and Table 2.

ENVIRONMENTAL CHARACTERISTICS

OPERATING TEMPERATURE (35V INPUT MAX.):

KDA 24A:

-10 to +60°C (all orientations)

KDA 24R:

-10 to +50°C (100% load, Figure 7)

-10 to +60°C (60% load, Figure 7)

-10 to +30°C (mounting other than

shown in Figure 4.)

STORAGE TEMPERATURE: -25°C to +85°C

COOLING: Natural convection.

GENERAL CHARACTERISTICS

ISOLATION VOLTAGE:

Between input and ground: 500V.
Between output and ground: 500V.
Relay contacts are galvanically isolated.

SAFETY: All units designed to meet UL 508, UL

60950, TÜV Rheinland EN60950 and EN 60529 (category

IP 20); KDA 24 units are CE marked per the Low Voltage

Directive (LVD), EN60950.

CONNECTIONS: Screw terminals: M3 slotted (use

cabinet tip screwdriver, flat, (0.125” [3mm] x 0.020”

[0.5mm]); Wire gage: solid/stranded AWG (mm

2

): 24-12

(0.25-2.5); strip length: 5/16 in. [8mm], max torque: 5 lb.-in

[0.5Nm].

WARRANTY: One year.

WEIGHT:

KDA 24A: 0.5 lbs. (0.255 kg.)

KDA 24R: 1.0 lbs. (0.454 kg.)

DIMENSIONS:

See Figure 6.

TABLE 1. FEATURE SUMMARY, KDA 24 SERIES

SPECIFICATION

KDA 24A

Independent

KDA 24R

Parallel Redundant

Reverse Voltage Protection

Yes

Yes

ORing (blocking) diodes

No

Yes

Undervoltage LED

Yellow = Alarm

Yellow = Alarm

Overvoltage LED

Red = Alarm

Red = Alarm

Input DC OK LED

Green = DC OK

Green = DC OK