beautypg.com

Figure 1. kda 24 series component locations, Kda 24r kda 24a – KEPCO KDA 24V Alarm Module User Manual

Page 2

background image

2

228-1694 REV 4

062411

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102

http://www.kepcopower.com email: [email protected]

FIGURE 1. KDA 24 SERIES COMPONENT LOCATIONS

+

-

-

+

B

A

VOLTAGE LIMIT ADJ.

HIGH

HIGH

LOW

LOW

A B

A

B

DC OK

COM

OK

COM

FAIL

A

OV

UV

UV

OV

B

OK

FAIL

3043505

LEGEND:

3

4

1

2

5

6

8

7

9

11

10

Note: Channels A and B are Identical.

CHANNEL B

CHANNEL A

5

8

6

7

9

11

4

3

2

1

11

9

8

7

6

5

4

3

2

1

IN+ Terminal (KDA 24R only)

Wire routed from bottom; see appropriate connection

diagram.

V- Terminal
Wire routed from bottom; see appropriate connection

diagram.

OUT+ Terminal (KDA 24R only)

V+ Terminal (KDA 24A only)
Wire routed from bottom; see appropriate connection

diagram.

LOW trimpot

Adjusts undervoltage (UV) setpoint.

HIGH trimpot

Adjusts overvoltage (OV) setpoint.

DC OK Indicator
Lights green when input voltage is within HIGH and
LOW settings.
Light goes off if alarm detected.

FAIL Terminal (Alarm Relay N.C contact)
Relay deenergizes for alarm; provides

connection from COM to FAIL. Wire routed from
top.

OK Terminal (Alarm Relay N.O contact)

Relay normally energized when input power OK;

provides connection from COM to OK. Wire
routed from top.

COM Terminal (Alarm Relay Common)
Wire routed from top.

OV Indicator

Lights red when input voltage is above HIGH

setting.

UV Indicator

Lights yellow when input voltage is below LOW

setting.

1

2

3

4

5

6

7

8

9

11

1

2

3

4

11

7

6

9

8

5

10

10

FAIL

OK

B

OV

UV

UV

OV

A

FAIL

COM

OK

COM

OK

DC

B

A

B

A

LOW

LOW

HIGH

HIGH

VOLTAGE LIMIT ADJ.

+

+

-

+

-

+

B

A

KDA 24R

KDA 24A

CHANNEL B

Note: Channels A and B are Identical.

CHANNEL A