beautypg.com

Figure 7. connections for remote voltage control, 3 vdc on/alarm indicator power options, 5 remote on-off – KEPCO HSF 300W Series (no suffix, suffix M and MZ) Operator Manuals User Manual

Page 12: Connections for remote voltage control, Dip switch settings for vdc on/alarm power options, R. 3.4.3), R 3.4.3), r, Able 5 for, R. 3.4.3), the output, E 7. at the ra

background image

10

HSF (M) 300W 030413

FIGURE 7. CONNECTIONS FOR REMOTE VOLTAGE CONTROL

3.4.3 VDC ON/ALARM INDICATOR POWER OPTIONS

To use the internal power supply reference voltage to power the VDC ON/ALARM indicator, set
Position 7 of SW1 to ON and Position 8 of SW2 to OFF (default) (see Figure 8A). Load effect is
±1% maximum. To use the HSF output voltage to power the VDC ON/ALARM indicator, set Posi-
tion 7 of SW1 to OFF and Position 8 of SW2 to ON (see Figure 8B). Load effect is ±0.6% maxi-
mum, however the minimums specified in Table 5 must be observed for the indicator to function.

FIGURE 8. DIP SWITCH SETTINGS FOR VDC ON/ALARM POWER OPTIONS

Table 5 lists the minimum HSF output voltage required to maintain VDC ON indicator function for
this case. Maximum output voltage of unit might cause overvoltage trip if SW2, position 8 is
enabled. If this occurs, turn Vadj trim pot counterclockwise to reduce output voltage, then reset the
unit.

3.5

REMOTE ON-OFF
When power is ON at the source, the output may be turned ON or OFF using the ±RC signals if
the remote ON-OFF feature is enabled. Note that when remote ON-OFF is enabled, the RESET
OUTPUT switch does not function. Remote ON-OFF is enabled by setting DIP switch positions 3
and 4 as shown in Figure 9B. The +RC and –RC signals (at the rack adapter I/O connector, pins
15 and 8, respectively) then turn the unit on or off. These pins accept a logic level (2.4V to 24V

TABLE 5. CONDITIONS FOR VDC ON/ALARM LED OPERATION POWERED BY

OUTPUT

MODEL

HSF 5-60M

HSF 12-53MZ

HSF 15-43MZ

HSF 24-27MZ

HSF 28-23MZ

HSF 48-13MZ

Minimum HSF output voltage
required for VDC ON LED to
function when SW 2 position 8 is
ON and SW 1 position 7 is OFF
(Volts d-c).

3.3

3.3

3.5

4.5

5

8

3043492

7

7 DC ON PWR BY REF

7

SW1

8

SW2

8

OFF

ON

OFF

ON

USE REFERENCE SUPPLY

(FACTORY DEFAULT)

TO POWER "DC ON"

A

TO POWER "DC ON"

USE HSF OUTPUT VOLTAGE

B

(REQUIRES MINIMUM OUTPUT VOLTAGE)

7
8

8

SW1

7

SW2

OFF

ON

ON

OFF

DC ON PWR BY OUTPUT V 8

8

7

7
8

8

7

TAB