Caution – HT instruments MPP300 User Manual
Page 25
MPP300
EN - 23
8.2. REFERENCE
STANDARDS
Instrument safety:
IEC/EN61010-1
Safety of measuring accessories:
IEC/EN61010-031
Technical documentation:
IEC/EN61187
Insulation: double
insulation
Mechanical protection:
IP 40
Pollution level:
2
Measurement category:
CAT III 1000V DC, Max 1000V between DC inputs
CAT IV 300V AC to earth, max 600V between AC inputs
8.3. GENERAL
CHARACTERISTICS
Memory
Memory capacity:
2 MBytes
Integration Period:
5,10,30,60,120,300,600,900,1800,3600s
Battery duration (with SOLAR-02): approx. 1.5 hours (@ PI = 5s)
approx. 8 days (@ PI = 600s)
Characteristics of radio module
Frequency range:
2.400
2.4835GHz
R&TTE category:
Class 1
Max transmission power:
30
W
Max RF connection distance:
1m (39in)
Power supply
Internal power supply:
Internal rechargeable Li-ION battery (3.7V, 1900mAh)
Battery duration >3 hours
External power supply:
AC/DC power supply 100
240VAC/50-60Hz – 5VDC
Mechanical characteristics
Dimensions (L x W x H):
300 x 265 x 140mm ; (12 x 10 x 6in)
Weight (batteries included):
1.2kg (2lv)
8.4. ENVIRONMENTAL
CONDITIONS FOR USE
Reference temperature:
23° ± 5°C (73° ± 41°F)
Operating temperature:
0 ÷ 40°C (32 ÷ 104°F)
Allowable relative humidity:
<80%HR
Storage temperature:
-10 ÷ 60°C (14 ÷ 140°F)
Storage humidity:
<80%HR
Max operating altitude:
2000m (*) (6562ft)
CAUTION
(*) Prescriptions for the use of the instrument at altitudes between 2000 and 5000m
As regards inputs, the instrument must be considered as downgraded to overvoltage
category CAT II 1000V DC and CAT III 300V to earth max 1000V between inputs. The
marks and symbols found on the instrument are valid only when the instrument is used at
altitudes <2000m
This instrument satisfies the requirements of Low Voltage Directive 2006/95/EC
(LVD) and of EMC Directive 2004/108/EC
8.5. ACCESSORIES
See the attached packing list