Sensor specific data, Table 3 sensor specific data, Table 3) – Detcon DM-100 User Manual
Page 33: 2 sensor specific data

Model DM-100
DM-100 Instruction Manual
Rev. 3.3
Page 29 of 40
Analog Output:
Linear 4-20mA DC current
750 ohms maximum loop load @ 24VDC
1.2 mA
All Fault Diagnostics (without display)
2mA
Sensor in calibration (without display)
3.25mA
All Fault Diagnostics (with display)
3.5mA
Sensor in calibration (with display)
4-20 mA
0-100% full-scale
22 mA
Over-range condition
Cable Requirements:
Power/Analog: 2-wire shielded cable
Maximum distance is 13,300 feet with 14 AWG
Mechanical Specifications
Length:
5.165 inches (131 mm), 8.5 inches (215mm) with Splash Guard
Width:
2.2 inches (55 mm)
Weight:
2.5 lbs (1.2 Kg)
Mechanical Connection:
3
/
4
" Male NPT threaded connection with locking nut
Electrical Connection:
four 18 gauge wire leads - 5.5" long
8.2 Sensor Specific Data
Table 3 Sensor Specific Data
Gas
GasName
Part Number
Response
Time
(seconds)
SpanDrift
Temperatur
e Range °C
Humidity
Range%
Warranty
O
2
Oxygen
371-343400-025
T95<30
<5%signal loss/year
-20 to+50
15 to 90
2 years
C
2
H
3
O
Acetyldehyde
371-12EA00-100
T90<140
<5%signal loss/year
-20 to+50
15 to 90
2 years
C
2
H
2
Acetylene
371-12EG00-100
T90<140
<5%signal loss/year
-20 to+50
15 to 90
2 years
C
3
H
3
N
Acrylonitrile
371-12EM00-100
T90<140
<5%signal loss/year
-20 to+50
15 to 90
2 years
NH
3
Ammonia
371-171700-100
T90<90
<2%signal
loss/month
-20 to+50
15 to 90
2 years
AsH
3
Arsine
371-191900-001
T90<60
<5%signal
loss/month
-20 to+40
20 to 95
1.5 years
Br
2
Bromine
371-747500-005
T90<60
<2%signal
loss/month
-20 to+50
15 to 90
2 years
C
4
H
6
Butadiene
371-12EB00-100
T90<140
<5%signal loss/year
-20 to+50
15 to 90
2 years
CO
Carbon
Monoxide
371-444400-100
T90=30
<5%signal loss/year
-40 to+50
15 to 90
3 years
Cl
2
Chlorine
371-747400-010
T90<60
<2%signal
loss/month
-20 to+50
15 to 90
2 years
ClO
2
(>10ppm) Chlorine Dioxide 371-777700-001
T90<60
<2%signal
loss/month
-20 to+50
15 to 90
2 years
ClO
2
(<=10ppm)
Chlorine Dioxide 371-282800-050
T90<120
<1%signal
loss/month
-20 to+40
10 to 95
2 years
B
2
H
6
Diborane
371-192100-005
T90<60
<5%signal
loss/month
-20 to+40
20 to 95
1.5 years
C
2
H
5
OH
Ethanol
371-12EO00-100
T90<140
<5%signal loss/year
-20 to+50
15 to 90
2 years
C
2
H
5
SH
Ethyl Mercaptan 371-24EZ00-100
T90<45
<2%signal
loss/month
-40 to+50
15 to 90
2 years
1
The last three digits of the Part Number are the range of the sensor cell. I.E. "-100" is a 100ppm range.