Field wiring, Figure 12 typical installation, Figure 12 – Detcon DM-100 User Manual
Page 14: 6 field wiring, Male npt plugs. detcon supplies one
Model DM-100
DM-100 Instruction Manual
Rev. 3.3
Page 10 of 40
NOTE
A conduit seal is typically required to be located within 18" of the J-Box and Sensor
Assembly. Crouse Hinds type EYS2, EYD2 or equivalent are suitable for this purpose.
NOTE
The Detcon Warranty does not cover water damage resulting from water leaking into the
enclosure.
Drain
Conduit
"T"
EYS Seal Fitting
DETCON, INC.
H2S
100 PPM
DM-100
Model 100
Figure 12 Typical Installation
NOTE
Any unused ports should be blocked with suitable
3
/
4
" male NPT plugs. Detcon supplies one
3
/
4
" NPT male plug with each J-box enclosure. If connections are other than
3
/
4
" NPT, use
an appropriate male plug of like construction material.
2.6 Field Wiring
Detcon Model DM-100 sensor assemblies require two conductor connections between power supplies and host
electronic controller’s 4-20mA input. Wiring designations are PWR and mA (sensor signal).
NOTE
Shielded cable is required for installations where cable trays or conduit runs include high
voltage lines or other possible sources of induced interference. Separate conduit runs are
highly recommended in these cases.
NOTE
The supply of power should be from an isolated source with over-current protection.
Terminal Connections – with Junction Box Option
CAUTION
Do not apply System power to the sensor until all wiring is properly terminated.
Refer to Section 2.7, Initial Start Up.