Field wiring, Figure 12 typical installation, Figure 12 – Detcon DM-100 User Manual

Page 14: 6 field wiring, Male npt plugs. detcon supplies one

background image

Model DM-100

DM-100 Instruction Manual

Rev. 3.3

Page 10 of 40

NOTE

A conduit seal is typically required to be located within 18" of the J-Box and Sensor
Assembly. Crouse Hinds type EYS2, EYD2 or equivalent are suitable for this purpose.

NOTE

The Detcon Warranty does not cover water damage resulting from water leaking into the
enclosure.

Drain

Conduit

"T"

EYS Seal Fitting

DETCON, INC.

H2S

100 PPM

DM-100

Model 100

Figure 12 Typical Installation

NOTE

Any unused ports should be blocked with suitable

3

/

4

" male NPT plugs. Detcon supplies one

3

/

4

" NPT male plug with each J-box enclosure. If connections are other than

3

/

4

" NPT, use

an appropriate male plug of like construction material.

2.6 Field Wiring

Detcon Model DM-100 sensor assemblies require two conductor connections between power supplies and host
electronic controller’s 4-20mA input. Wiring designations are PWR and mA (sensor signal).

NOTE

Shielded cable is required for installations where cable trays or conduit runs include high
voltage lines or other possible sources of induced interference. Separate conduit runs are
highly recommended in these cases.

NOTE

The supply of power should be from an isolated source with over-current protection.

Terminal Connections – with Junction Box Option

CAUTION

Do not apply System power to the sensor until all wiring is properly terminated.
Refer to Section 2.7, Initial Start Up.