Specifications – Detcon DM-200 User Manual
Page 33
Model DM-200
DM-200 Instruction Manual
Rev. 2.0
Page 29 of 40
9. Specifications
Sensor Type:
Continuous diffusion/adsorption type
3-Electrode Electrochemical Sensor (2-Electrode for O
2
)
Plug-in Replaceable Type
Sensor Life:
2 years typical
Measuring Ranges:
0-1 ppm up to 0-10,000 ppm (Toxic Gasses)
0-1%
up
to
0-25%
volume
(O
2
)
Accuracy/ Repeatability:
±2% of full-range (Toxic Gasses)
±1%
of
full-range
(O
2
)
Response Time:
T90 < 30 seconds typical (See Sensor Table)
Environmental Specifications
Operating Temperature:
-40°C to +50°C typical (See Table 3)
Storage Temperature:
-40°C to +50°C typical (See Table 3)
Operating Humidity:
10-95% RH Continuous Duty (See Table 3)
0-100%
RH
Short-Term
Duration
Only
Operating Pressure:
Ambient ±10%
Electrical Specifications
Input
Voltage:
11.5-30
VDC
Power Consumption
Normal operation = 4 mA (0.1 watts @ 24VDC);
Maximum = 20 mA (0.5 watts @ 24VDC)
RFI/EMI Protection:
Complies with EN61326
Analog Output:
Linear 4-20mA DC current
1000
ohms
maximum
loop
load
@
24VDC
3.5 mA All Fault Diagnostics
3.5 mA In-Calibration
4-20 mA 0-100% full-scale
Mechanical Specifications
Length:
12.5 inches (317.5 mm), Includes Splashguard
Width:
6.0
inches
(152.5
mm)
Weight:
5.6
lbs
(2.5
Kg)
Mechanical Connection:
¾” Male NPT threaded connection