3.4.3 Program Mode

The program mode provides a program status menu, allows for the adjustment of alarm set point levels, and the

selection of the calibration gas level setting..

3.4.3.1 Program Status

The program status scrolls through a menu that displays:

* The gas type, range of detection and software version number. The menu item appears as:

“CO2 RANGE V6.0”

* The alarm set point level of alarm 1. The menu item appears as:

“ALM1 SET @ ##%”

* The alarm f iring direction of alarm 1. The menu item appears as:

“ALM1 ASCENDING” or descending.

* The alarm relay latch mode of alarm 1. The menu item appears as:

“ALM1 NONLATCHING” or latching.

* The alarm relay energize state of alarm 1. The menu item appears as:

“ALM1 DE-ENERGIZED” or energized.

* The alarm set point level of alarm 2. The menu item appears as:

“ALM2 SET @ ##%”

* The alarm f iring direction of alarm 2. The menu item appears as:

“ALM2 ASCENDING” or descending.

* The alarm relay latch mode of alarm 2. The menu item appears as:

“ALM2 LATCHING” or nonlatching.

* The alarm relay energize state of alarm 2. The menu item appears as:

“ALM2 DE-ENERGIZED” or energized.

* The alarm relay latch mode of the fault alarm. The menu item appears as:

“FLT NONLATCHING” or latching.

* The alarm relay energize state of the fault alarm. The menu item appears as:

“FLT ENERGIZED” or deenergized.

* The calibration gas level setting. The menu item appears as:

“CalLevel @ #.##%”

* Identif ication of the RS-485 ID number setting. The menu item appears as:

“485 ID SET @ ##”

* Sensor temperature in °C appears as:

“TEMPERATURE ## °C”

* The estimated remaining sensor life. The menu item appears as:

“OPTICS AT 100%”

3.4.3.2 Alarm 1 Level Adjustment

The alarm 1 level is adjustable over the range 10 to 90% of full-scale range. For CO2 gas sensors, the level is factory
set at 20% of full-scale range. The menu item appears as:

“SET ALM1 @ #.##%”

3.4.3.3 Alarm 2 Level Adjustment

The alarm 2 level is also adjustable over the range 10 to 90% of full-scale range. For CO2 gas sensors, the level is
factory set at 60% of full-scale range. The menu item appears as:

“SET ALM2 @ #.##%”

3.4.3.4 Calibration Level Adjustment

The Calibration level is adjustable from 10% to 90% of full-scale range. The menu item appears as:

“CalLevel @ #.##%”

3.5 I

NSTALLATION

Optimum performance of ambient air/gas sensor devices is directly relative to proper location and installation practice.

3.5.1 Field Wiring Table (4-20 mA output)

Detcon Model IR-640/IR-642 CO2 sensor assemblies require three conductor connection between power supplies

and host electronic controllers. Wiring designators are + (DC), (DC) , and mA (sensor signal). Maximum single

conductor resistance between sensor and controller is 10 ohms. Maximum wire size for termination in the sensor

assembly terminal board is 14 gauge.

AWG

Meters

Feet

20

240

800

18

360

1200

16

600

2000

14

900

3000

Note 1: This wiring table is based on stranded tinned copper wire and is designed to serve as a reference only.

Note 2:

Shielded cable may be required in installations where cable trays or conduit runs include high voltage

lines or other sources of induced interference.

Note 3:

The supply of power must be from an isolating source with over-current protection as follows:

AWG

Over-current Protection

AWG

Over-current Protection