beautypg.com

Detcon IR-642 User Manual

Page 19

background image

to the RS-485 ID number would require the sensor housing to be opened, thus declassif ication of the area would

be required. See section 3.5.4-f for details on changing the RS-485 ID number.

The following section explains the details of the Modbus™ protocol that the IR-622 MicroSafe™ sensor supports.

Code 03 - Read Holding Registers, is the only code supported by the transmitter. Each transmitter contains 6 hold-

ing registers which ref lect its current status.

Register #

High Byte

Low Byte

40000

Gas type

Sensor Life

Gas type is one of the following:

01=CO, 02=H2S, 03=SO2, 04=H2, 05=HCN, 06=CL2, 07=NO2, 08=NO, 09=HCL, 10=NH3, 11=LEL, 12=O2

Sensor life is an estimated remaining use of the sensor head, between 0% and 100%

Example: 85=85% sensor life

Register #

High Byte

Low Byte

40001

Detectable Range

i.e. 100 for 0-100 ppm, 50 for 0-50% LEL, etc.

Register #

High Byte

Low Byte

40002

Current Gas Reading

The current gas reading as a whole number. If the reading is displayed as 23.5 on the display, this register would

contain the number 235.

Register #

High Byte

Low Byte

40003

Alarm 1 Setpoint

This is the trip point for the f irst alarm.

Register #

High Byte

Low Byte

40004

Alarm 2 Setpoint

This is the trip point for the second alarm.

Register #

High Byte

Low Byte

40005

Status Bits

Status Bits

High Byte

Bit 7

Not used, always 0

Bit 6

Not used, always 0

Bit 5

Not used, always 0

Bit 4

Not used, always 0

Bit 3

1-Unit is in calibration

0-Normal operation

Bit 2

1-Alarm 2 is ascending

0-Alarm 2 is descending

Bit 1

1-Alarm 2 is normally energized

0-Alarm 2 is normally de-energized

Bit 0

1-Alarm 2 is latching

0-Alarm 2 is non-latching

Low Byte

Bit 7

1-Alarm 2 Relay is energized

0-Alarm 2 Relay is not energized

Detcon Model IR-640/IR-642 Carbon Dioxide Sensor PG.19

This manual is related to the following products: