beautypg.com

Supervisory mode – Condec DPDG User Manual

Page 6

background image

configuration. This is accomplished through a password protected

“supervisory mode”. Press ENTER to access the supervisory

mode, or CONFIG to return to normal operation.

Supervisory Mode

Press ENTER when “FUnC LOCK” is displayed, 0PWRD will be

displayed on the gauge. The password to enter supervisory mode is

101, set using the ▲ and ▼ keys. Holding a key continuously will

cause the display to advance more quickly for faster setting. The

password is factory set and cannot be changed
1. Your CONDEC DPDG is shipped from the factory with all setting

access “unlocked” or available to be changed.

2. In supervisory mode each of the parameters can be locked or

unlocked using the ▲ and ▼ keys. Select LOC (lock) for those

parameters you do not want to be accessible, and UnLOC (unlock)

for those can be accessed.

3. In order, the functions that can be unlocked, locked or accessed

are:

• Zero function (enable/disable)

• Set pressure units (enable/disable)

• Auto shutdown adjustment (enable/disable)

• Damping settings (enable/disable)

• Sample rate setting (enable/disable)

• Tare setting (enable/disable)

• Custom engineering units (set scale factor)

4. Use the CONFIG key to scroll through the above choices, and the

and ▼ keys to lock and unlock features. Press CONFIG to

continue scrolling through the parameters, pressing ENTER at any

point saves your settings and returns the gauge to normal

operation.

When a function is “locked, it cannot be accessed or changed

from its current state. To change a locked function, enter the

supervisory mode, and unlock the function. Once it is changed,

you may enter supervisory mode to lock access again.

5. Setting a custom engineering unit or scale: The last menu choice

in supervisory mode is SET FACTR. This allows you to set a

multiplier factor from 0.001 to 100, creating a custom scale. The

set factor will be multiplied by the PSI measured, the result will be

displayed.

For example: 40 PSI is the equivalent of 1000 lbs of product in a

tank. You want to display the product weight , using a 100 PSI

5