Environmental considerations, Rack considerations, Environmental considerations rack considerations – Brocade 6520 Hardware Reference Manual User Manual
Page 20
![background image](/manuals/361679/20/background.png)
8
Brocade 6520 Hardware Reference Manual
53-1002705-02
Installation and safety considerations
2
Environmental considerations
For successful installation and operation of the switch, ensure that the following environmental
requirements are met:
•
At a minimum, adequate cooling requires that you install the switch with the intake side, as
indicated by the airflow direction of the fan assemblies, facing the cool-air aisle.
The chassisshow output indicates “Reverse” for non-port side intake and “Forward” for port
side intake.
•
All equipment in the rack should force air in the same direction to avoid intake of exhaust air.
•
Airflow requirements outlined in
must be met. Note that the requirements differ based
on the direction of the airflow.
•
The ambient air temperature does not exceed 40
°
C (104
°
F) while the switch is operating.
lists the acceptable environmental ranges for both operating and nonoperating (such as
during transportation or storage) conditions.
Rack considerations
For successful installation and operation of the switch in a rack, ensure the following rack
requirements are met:
•
The rack must be a standard EIA rack.
•
A rack space that is two rack units (2U) high; 8.90 cm (3.50 inches) high and 48.3 cm (19
inches) wide.
•
There are three rack kit options that accommodate the Brocade 6520, a four-post fixed rack
kit, a two-post Telco rack kit, and a four-post sliding rail rack kit. See their respective
installation manuals for details.
TABLE 5
Environmental requirements
Condition
Acceptable during operation
Acceptable during non-operation
Ambient
temperature
0º to 40ºC (32º to 104ºF)
-25º to 70ºC (-13º to 158ºF)
Humidity
10% to 85% RH non-condensing, at
40ºC (104ºF)
10% to 90% RH non-condensing, at 70ºC
(158ºF)
Altitude
0 to 3 km (9,842 feet) above sea level
0 to 12 km (39,370 feet) above sea level
Shock
20 G, 6 ms, half-sine wave
33 G, 11 ms, half-sine wave, 3/eg Axis
Vibration
0.5 G sine, 0.4 gms random, 5-500 Hz
2.0 G sine, 1.1 gms random, 5-500 Hz
Air flow
Port side exhaust -
Maximum - 176.7 cmh (104 cfm)
Nominal - 52.7 cmh (31 cfm)
Port side intake -
Maximum - 185.2 cmh (109 cfm)
Nominal - 56.1 cmh (33 cfm)
N/A
Heat dissipation
1378.5 BTU/hr (no optics configuration)
1706.1 BTU/hr (fully populated port
configuration)
N/A