LOW TEMPERATURE

WARNING TERMOSTAT

CLOSE @ 32°F

OPEN @ 50°F

ALUMINUM MOUNTING PLATE

TERMINAL BLOCK
(4 WIRE CONNECTION)

LED CONTROL

THERMOSTAT HOLDER

RESISTOR HEATER

OVER TEMP SAFETY

THERMOSTAT

OPEN @ 120°F

CLOSE @ 90°F


LOW

TEMP

POWER


THUMB LOCK

629723 HINGED COVER

629721A FRAME

06297F-M BACK BOX

SUB 7500-HTR ASSEMBLY 1/8 in.

CONTROL THERMOSTAT

CLOSED @ 50°F OPEN @ 70°F

STANDOFF MALE FEMALE

#8-32 x 3/8”

19051 (4)

#8-32 x 3/8 FLAT

HEAD MS

“HEAT ON” RED LED

“POWER ON” GREEN LED

ADDITIONAL EYELET FOR SECONDARY LOCK


DEVICE WIRING ACCESS HOLE

ELECTRONIC DEVICE

MOUNTING HOLES

ILLUSTRATION 3

ILLUSTRATION 4

Safety Technology International, Inc.

2306 Airport Road • Waterford, Michigan 48327-1209
Phone: 248-673-9898 • Fax: 248-673-1246
Toll Free: 800-888-4784 • E-mail: [email protected]
Web: www.sti-usa.com

Safety Technology International (Europe) Ltd.

Unit 49G Pipers Road • Park Farm Industrial Estate • Redditch
Worcestershire • B98 0HU • England • Tel: 44 (0) 1527 520 999
Fax: 44 (0) 1527 501 999 • Freephone: 0800 085 1678 (UK only)
E-mail: [email protected] • Web: www.sti-europe.com

5. Mount the heater plate assembly to the back box with

control thermostat toward bottom of enclosure (see
Illustration 4). Be sure to route wires for electronic device
through the hole in the center of the heater plate before
attaching heater plate. For vertical mounting (hinges to
right or left side) be sure control thermostat is towards
the bottom of the enclosure.

6. Connect the electronic device and mount to the heater

plate in mounting holes indicated using #6 - 32 x 1/2”
screws (2) provided.

NOTE: If moisture buildup occurs, drill a weep

hole on bottom side of back box.

4. Connect heater power and control wires. Note: Terminals are not

polarity sensitive.

a. Connect low temperature monitor terminals to supervisory panel

if used (see Illustration 3).

b. Connect power terminals to power source. 12-24 volt AC/DC.

• Heating capacity is determined by input voltage. Be sure

the power source has enough capacity to support the load
at the input voltage.

12 Volt, 19 WATTS

16.5 Volt, 36 WATTS

24 Volt, 77 WATTS

• 16.5 VAC adapter included