Non-Preferred Pump Location: The pump must be located with at least 1 metre

flooded suction at all times.

If it is not possible to locate the pump in the preferred area due to site limitations

and it is necessary to position the unit in the loft, or in a position above the

secondary tapping that feeds the pump, then there is an increased risk of air

locks. This risk must be eliminated.

The following method will help to overcome the problem:

In this application only use an Essex or Techflow side entry flange, then fit a “U”

bend or downward loop in the supply pipe to the pump of 350 mm depth before

rising to the pump should ensure the cylinder vents its air up the expansion pipe,

not up the pump feed (Fig. 6).

3 PUMP

CONNECTIONS

3.11

Hose to pump: These pumps have G 1 threaded connections to accept the

hoses supplied. The hose end is made water tight with a sealing washer on

assembly, nip tight to 4/5 Nm for water tight seal (

Do not overtighten).

3.12

Hose to pipework: Hoses terminating in G 1 threaded connections are supplied

and when securing the male end to a suitable pipe fitting, seal with PTFE tape or

other suitable sealant.

Max. inlet head

10

m

Min. inlet head

1

m

350

mm

min.

200

mm

min.

Least preferred area

Fig. 6