2 location - hot water 2 location - cold water – Stuart Turner Monsoon U2.0 bar Single User Manual
Page 7
![background image](/manuals/360707/7/background.png)
- 7 -
Cont ...
2.27
The cold water supply: The supply must be air free and have a dedicated
connection to the tank which should be via a tank connector, positioned at a
slightly lower level (25 mm minimum) than the feed pipe to the hot water cylinder.
Do not connect to the mains.
2.28
Location: The pump must, for optimum performance, be sited as close as
possible to and never more than 4 metres from the HOT WATER cylinder. The
pump should always be sited BELOW the HOT WATER take-off from the cylinder.
2 LOCATION - HOT WATER
2 LOCATION - COLD WATER
Table 1
Model
Min.
static
inlet
head
(m)
Max.
static
inlet
head
(m)
Max.
static
outlet
head
(m)
U2.0 bar Single
0.5
8
8
U3.0 bar Single
0.5
12
12
U4.5 bar Single
Fig. 4
Static Inlet Pressure
(see table 1)
Static Outlet Pressure (see table 1)
Fig. 5
Static Inlet Pressure
(see table 1)
Static Outlet Pressure (see table 1)