Three easy steps – Thermolec Application &Technical Notes User Manual
Page 7

THREE EASY STEPS
STEP 1 - (continued)
Power and Voltage Requirements
Nominal and Standard Supply Voltages
While a utility's voltage may be referred to by means of a nominal figure, actual applied voltage may vary
over a fairly wide range depending on factors like the system's power distribution lines, and many others.
For instance, a nominal voltage of 575V / 3PH / 60Hz may variously be called 550V, 575V or 600V
depending more on what the specification writer is accustomed to calling it than on the actual voltage
supplied to the heater. Designing a heater for 550V when in fact 600V is supplied to it will result in almost
10% more current and 20% more KW capacity since current is proportional to the voltage and KW is
proportional to the square of the voltage. Conversely, application of a lower voltage results in a
corresponding under-performance of the heater. It is therefore of the utmost importance to ensure that
the correct voltage is specified.
For safety reasons Thermolec standard supply voltages have been chosen to be the highest for each
voltage range, as shown in the table below. Heaters designed for lower voltages in each range are
available and will be supplied when customer expressly specifies a lower supply voltage.
STANDARD VOLTAGES
This standardization reduces the risk of overheating due to a heater subjected to an overvoltage with the
resulting nuisance tripping of high-temperature cut-outs.
Examples of risk:
Example 1:
A 575V/3 PH heater in a 600V/3PH installation would carry 5% more current and produce 10% more KW
than it is designed for.
Example 2:
A 220V/1 PH heater in a 240V/1PH installation would carry 10% more current and produce 20% more
KW than it is designed for.
Under such conditions, these heaters would overheat and thermal cut-outs would trip.
In order to avoid any risk of overheating, it would be advisable to verify the existing conditions
on the job site.
In case of doubt about the required voltage, always specify one of the Thermolec Standard Voltages.
Common
110
230
318
440
550
Nominal
115
208
220
240
277
332
380
416
460
575
Voltages
120
347
480
600
Thermolec
Standard
120
208
208
220
240
240
277
347
380
380
416
416
480
480
600
600
Voltages
1 Ph
1 Ph
3 Ph
1 Ph
1 Ph
3 Ph
1 Ph
1 Ph
1 Ph
3 Ph
1 Ph
3 Ph
1 Ph
3 Ph
1 Ph
3 Ph