HYBRID CONTROL - Binary Mode

Binary staging for a 160 KW heater.
SCR Step

1/16

10 KW

Step 1

1/16

10 KW

Step 2

2/16

20 KW

Step 3

4/16

40 KW

Step 4

8/16

80 KW

In this example, the control voltage 0-10 Volts DC is divided by 16 which gives an increment of
0.625 Volts per 10 KW step.

Here is how it works, in increments of 10 KW and .625 V input voltage:

Input voltage

KW output

Fixed steps on and SCR

from 0 to .625 V

0 to 10 KW

The variable SCR step covers the heat demand

from .625 to 1.25 V

10 to 20 KW

step 1 + SCR (10 fixed + 10 SCR)

from 1.25 to 1.875 V

20 to 30 KW

step 2 + SCR (20 fixed + 10 SCR)

from 1.875 to 2.5 V

30 to 40 KW

step 1 + step 2 + SCR (30 fixed + 10 SCR)

from 2.5 to 3.125 V

40 to 50 KW

step 3 + SCR (40 fixed + 10 SCR)

from 3.125 to 3.75 V

50 to 60 KW

step 3 + step 1 + SCR (50 fixed + 10 SCR)

from 3.75 to 4.375 V

60 to 70 KW

step 3 + step 2 + SCR (60 fixed + 10 SCR)

from 4.375 to 5 V

70 to 80 KW

step 3 + step 2 + step 1+ SCR (70 fixed + 10 SCR)

from 5 to 5.625 V

80 to 90 KW

step 4 + SCR (80 fixed + 10 SCR)

from 5.625 to 6.25 V

90 to 100 KW

step 4 + step 1 + SCR (90 fixed + 10 SCR)

from 6.25 to 6.875 V

100 to 110 KW

step 4 + step 2 + SCR (100 fixed + 10 SCR)

from 6.875 to 7.5 V

110 to 120 KW

step 4 + step 2 + step 1 + SCR (110 fixed + 10 SCR)

from 7.5 to 8.125 V

120 to 130 KW

step 4 + step 3 + SCR (120 fixed + 10 SCR)

from 8.125 to 8.75 V

130 to 140 KW

step 4 + step 3 + step 1 + SCR (130 fixed + 10 SCR)

from 8.75 to 9.375 V

140 to 150 KW

step 4 + step 3 + step 2 + SCR (140 fixed + 10 SCR)

from 9.375 to 10 V

150 to 160 KW

step 4 + step 3 + step 2 + step 1 + SCR (150 fixed + 10 SCR)

Since the SCR step is kept small, it is cost effective compared to a full SCR 160 KW.

Hybrid Binary Load Diagram (Please see next page)