Three easy steps – Thermolec Application &Technical Notes User Manual
Page 32

STEP 3 - (continued)
HYBRID CONTROL - Binary Mode
Binary staging for a 160 KW heater.
SCR Step
1/16
10 KW
Step 1
1/16
10 KW
Step 2
2/16
20 KW
Step 3
4/16
40 KW
Step 4
8/16
80 KW
In this example, the control voltage 0-10 Volts DC is divided by 16 which gives an increment of
0.625 Volts per 10 KW step.
Here is how it works, in increments of 10 KW and .625 V input voltage:
Input voltage
KW output
Fixed steps on and SCR
from 0 to .625 V
0 to 10 KW
The variable SCR step covers the heat demand
from .625 to 1.25 V
10 to 20 KW
step 1 + SCR (10 fixed + 10 SCR)
from 1.25 to 1.875 V
20 to 30 KW
step 2 + SCR (20 fixed + 10 SCR)
from 1.875 to 2.5 V
30 to 40 KW
step 1 + step 2 + SCR (30 fixed + 10 SCR)
from 2.5 to 3.125 V
40 to 50 KW
step 3 + SCR (40 fixed + 10 SCR)
from 3.125 to 3.75 V
50 to 60 KW
step 3 + step 1 + SCR (50 fixed + 10 SCR)
from 3.75 to 4.375 V
60 to 70 KW
step 3 + step 2 + SCR (60 fixed + 10 SCR)
from 4.375 to 5 V
70 to 80 KW
step 3 + step 2 + step 1+ SCR (70 fixed + 10 SCR)
from 5 to 5.625 V
80 to 90 KW
step 4 + SCR (80 fixed + 10 SCR)
from 5.625 to 6.25 V
90 to 100 KW
step 4 + step 1 + SCR (90 fixed + 10 SCR)
from 6.25 to 6.875 V
100 to 110 KW
step 4 + step 2 + SCR (100 fixed + 10 SCR)
from 6.875 to 7.5 V
110 to 120 KW
step 4 + step 2 + step 1 + SCR (110 fixed + 10 SCR)
from 7.5 to 8.125 V
120 to 130 KW
step 4 + step 3 + SCR (120 fixed + 10 SCR)
from 8.125 to 8.75 V
130 to 140 KW
step 4 + step 3 + step 1 + SCR (130 fixed + 10 SCR)
from 8.75 to 9.375 V
140 to 150 KW
step 4 + step 3 + step 2 + SCR (140 fixed + 10 SCR)
from 9.375 to 10 V
150 to 160 KW
step 4 + step 3 + step 2 + step 1 + SCR (150 fixed + 10 SCR)
Since the SCR step is kept small, it is cost effective compared to a full SCR 160 KW.
Hybrid Binary Load Diagram (Please see next page)
THREE EASY STEPS