STEP 3 - (continued)

Since the SCR step is kept relatively small (53.3 Kw ), it is still cost effective
compared to a full SCR 160 KW.

In the following graphic, the sequential loads are switched ON and OFF to match the heat demand.
Lay a straightedge vertically at any position of the control input voltage and find exactly which stages are
ON or OFF. The SCR not only fill the gaps but overlaps the gaps between the fixed steps at all times.

Hybrid Sequential Load Diagram