beautypg.com

How to select and specify in three easy steps, Three easy steps – Thermolec Application &Technical Notes User Manual

Page 5

background image

HOW TO SELECT AND SPECIFY IN THREE EASY STEPS

Selecting the heater for your application can be done in three easy steps:

1- Determine heater capacity, voltage and electrical components

2- Determine duct dimensions, air requirements and mechanical options

3- Determine method of control, then select control components

STEP 1 -

DETERMINE HEATER CAPACITY, VOLTAGE AND ELECTRICAL COMPONENTS

Heater capacity

Given CFM (volume of air in cubic feet per minute) and

D

ºT (temperature rise in º F ),

the KW capacity can be determined from the formulas:

NOTE:

The above formulas are for standard air. Consult your Thermolec representative for non-standard air

conditions.

* Maximum air temperature rise for which the heater is designed

** This formula is for quick calculation and contains a loss allowance of 5%.

THREE EASY STEPS

KW** =

CFM x Temperature Rise, ºF*

3000

Temperature Rise, ºF =

KW x 3000

CFM