Electrical connections, Thermo-air & thermo-zone – Thermolec Application &Technical Notes User Manual
Page 64

How to evaluate your heating requirement?
Considering today’s insulation standards, an easy to remember rule of thumb is that the
heating capacity should be equal to 8 watts per square foot. A 1 KW heater would then be
sufficient to heat a surface of 1000 ÷ 8 = 125 square feet. Adding a safety factor would bring
the surface to approximately 120 square feet, i.e. a 12’ x 10’ room.
We suggest:
Up to 120 sq. ft.
1 KW
from 121 sq. ft. to 240 sq. ft.
2 KW
from 241 sq. ft. to 360 sq. ft.
3 KW, and so on.
A small excess of capacity is not a problem because the electronic controller will modulate
this capacity in order to give only the heat required by the thermostat.
How to evaluate the ventilation requirements?
A THERMO-AIR or THERMO-ZONE requires a minimum of 30 CFM (cubic feet per minute)
per Kilowatt to operate.
A lower air flow is not a problem for the heater since the electronic controller will automatically
reduce the heating according to the air flow.
For a quick calculation, a 1 KW unit requires a minimum of 30 CFM,
a 2 KW unit requires a minimum of 60 CFM, and so on.
Electrical connections
We recommend not to exceed 2 KW at 120V, 5 KW at 208V, 6 KW at 240V, 7KW at 277V,
8KW at 347V.
THERMO-AIR & THERMO-ZONE