THREE EASY STEPS

STEP 2 - (continued)

Size Limitations

Although there are practically no limitations to the maximum size of Thermolec custom-built heaters, all
CSA listed heaters must comply to the following minimum dimensions:

Size Limitation Table

CSA listed custom heaters are available in virtually any KW rating. However, Thermolec listing is
restricted to a maximum KW density of 22.5 KW per square foot of heated area for open coil and 13 KW
per square foot for tubular. For a quick approximation of the maximum KW available in a particular duct
size, please use the following formulas:

Modular Construction for Air Handling Units

Thermolec heaters can be part of large
air handling units. In this case, a heater
becomes a module of a bigger unit and is
designed to match the other components:
filter frames, fans, cooling coils, VAV
boxes, etc. Flanged units can be bolted
directly to adjacent sections or slip-in
models are inserted into a bigger unit.
Since there can be several special
conditions in such big units, the heater
has to be designed to accommodate
them. Special features can be installed
upon request: section with no heat,
pressure plates to equalize air flow, buffer
sections to space the heater
away from other components, etc.

Modular Heating Sections

Slip-in Type

Flanged Type

Slip-in Type

Flanged Type

Open Coil

Open Coil

Tubular

Tubular

Minimum Duct Width

6”

5”

8”

7”

Dimension “W”

Minimum Duct Height

5”

4”

6”

6”

Dimension “H”

Open Coil Type

Maximum KW = 22.5 x width in inches x height in inches

SC or FC

144

Tubular Type

Maximum KW =

13 x width in inches x height in inches

ST or FT

144