Yokogawa Standalone MW100 User Manual
Page 8
8
IM CA150E
By clicking on ETHERNET-MODULE MW100 within the Controller Organizer tree, the connection can be fully confi gured. Note
- the IP Address should point to an MW100, Comm Format which defi nes what data types to use and Connection Parameters
which layout the inputs and outputs of the MW100. In this case, the connection is confi gured to communicate using double
precision integers to an MW100 at IP address 10.0.232.126 with inputs at Assembly Instance 130 (corresponding to Communi-
cation Channel C001-C010; 10 channels due to Size), and outputs at Assembly Instance 131 (corresponding to Communication
Channel C101-C110; 10 channels due to Size). The Size of the Input and Output Assembly Instance can range from 1 to 100
to encompass 100 Communication or Computation Channels in a block and 60 for I/O Channels. When using I/O Messaging,
there is a limit of 100 inputs and 100 outputs per MW100 (Explicit Messaging must be used to reach more MW100 channels).
Note a limit of 125 32-bit points per instance is the maximum data size that EIP allows for I/O Messaging.
Connection and Assembly Instance Confi guration in RSLogix 5000
®
The following diagram depicts the available Instance IDs, Sizes and Data Types that can be confi gured within a connection.
Table of MW100 Channels with corresponding Instance ID