• Nameplate for FM Intrinsically Safe/Explosionproof/Dust-Ignition-proof/Non-Incendive
type (Option /FU1)
Intrinsically Safe for Class I II, III; Groups A - G; Divisions 1 & 2;
Zone 20, Class I, Zone 0, AEx ia IIC T4 Ga -40°C < Ta < +80°C
Ui = 24V, Ii = 150mA, Pi = 0.65W, Ci = 0uF, Li = 0mH
Explosionproof/Dust-Ignition-Proof for Class I, II, III; Groups A - G;
Divisions 1 & 2
Class I, Zone 1, Group IIC, T4
Tamb. -40°C to 80°C
Non-Incendive for Class I, II, III; Groups A - D, F, G; Division 2
Class I, Zone 2, Group IIC
T4 Tamb. -40°C to 80°C
Enclosure: NEMA 4X
WARNING
WARNING: SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY.
WARNING: DO NOT OPEN COVERS WHEN AN EXPLOSIVE ATMOSPHERE
MAY BE PRESENT. INSTALL IN ACCORDANCE WITH THE INSTRUCTION
MANUAL.
ASSEMBLED IN USA WITH
FOREIGN AND DOMESTIC
PARTS
Conforms to: FM 3600,
FM 3610, FMRC 3611,
FM 3615, FM 3616, UL 913,
UL 1203, UL 60079-0,
UL 60079-11.
4 0 0 0 7 9 8
4-20mA DC
M1275DT
• Nameplate for ATEX Intrinsically Safe/Flameproof/Dustproof/Non-Incendive type (Option
/KU21)
Cert. No: ITS13ATEX27856X
Cert. No: ITS13ATEX17857
Cert. No: ITS13ATEX47858
II 1G Ex ia IIC T4 Ga
Ui = 24V, Ii = 150mA, Pi = 0.65W, Ci = 0uF, Li = 0mH
II 2G Ex d IIC T4 Gb
II 2D Ex tb IIC T135°C Db
II 3G Ex nA IIC T4 Gc
Tamb. -40°C to +80°C
Enclosure: IP66 and IP67
WARNING
AFTER DE-ENERGIZING, DELAY 5 MIN BEFORE
OPENING COVER. WHEN THE AMBIENT TEMP.
=
70°C,
USE HEATRESISTING CABLE RATED
=
90°C.
INSTALL IN ACCORDANCE WITH THE INSTRUCTION MANUAL.
0359
ASSEMBLED IN USA WITH
FOREIGN AND DOMESTIC
PARTS
4-20mA DC
M1275DU
• Nameplate for CSA Intrinsically Safe/Explosionproof/Dust-Ignition-proof/Non-Incendive
type (Option /CU1)
ASSEMBLED IN USA WITH
FOREIGN AND DOMESTIC
PARTS
4-20mA DC
Intrinsically Safe
(Securite Intrinseque) for Class I II, III; Groups A - G;
Divisions 1 & 2; Zone 20, Class I, Zone 0, AEx ia IIC T4 Ga -40°C < Ta < +80°C
Ui = 24V, Ii = 150mA, Pi = 0.65W, Ci = 0uF, Li = 0mH
Explosionproof/Dust-Ignition-Proof for Class I, II, III; Groups A - G;
Divisions 1 & 2
Class I, Zone 1, Group IIC, T4
Tamb. -40°C to 80°C
Nonincendive for Class I, II, III; Groups A - D, F, G; Division 2
Class I, Zone 2, Group IIC T4 Tamb. -40°C to 80°C
Enclosure: "Type 4X"
WARNING
WARNING: SUBSTITUTION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY
ADVERTISSEMENT: LA SUBSTITUTION DE COMPOSANTS PEUT
COMPROMETTRE LA SECURITE INTRINSEQUE.
WARNING: DO NOT OPEN COVERS WHEN AN EXPLOSIVE ATMOSPHERE
MAY BE PRESENT. INSTALL IN ACCORDANCE WITH THE INSTRUCTION
MANUAL. ATTENTION: NE PAS OUVRIR Si des explosifs ATMOSPHERE
peuvent être présents. INSTALLER EN SELON LE MODE D'EMPLOI.
4 0 0 0 7 9 8
Certified to: CSA-C22.2 No. 25,
CSA-C22.2 No. 30, CSA-C22.2
No. 157, CSA-C22.2 No. 213,
CSA-C22.2 No. 60079-0,
CSA-C22.2 No. 60079-11.
M1275DV
• Nameplate for IEC Intrinsically Safe/Flameproof/Dustproof/Non-Incendive type (Option
/SU2)
ASSEMBLED IN USA WITH
FOREIGN AND DOMESTIC
PARTS
Cert. No:
IECEx ETL 13.0028X
Cert. No:
IECEx ETL 13.0029
Cert. No:
IECEx ETL 13.0030
Ex ia IIC T4 Ga
Ui = 24V, Ii = 150mA, Pi = 0.65W, Ci = 0uF, Li = 0mH
Ex d IIC T4 Gb
Ex tb IIC T135°C Db
Ex nA IIC T4 Gc
Tamb. -40°C to +80°C
Enclosure: IP66 and IP67
WARNING
AFTER DE-ENERGIZING, DELAY 5 MIN BEFORE
OPENING COVER. WHEN THE AMBIENT TEMP.
=
70°C, USE HEATRESISTING CABLE RATED
=
90°C.
INSTALL IN ACCORDANCE WITH THE INSTRUCTION MANUAL.
4-20mA DC
M1275DW