11 pressure equipment directive (ped), 12 low voltage directive, Pressure equipment directive (ped) -13 – Yokogawa EJA310E User Manual
Page 21: Low voltage directive -13, Caution
<2. Handling Cautions>
2-13
IM 01C25B01-01E
2.11 Pressure Equipment
Directive (PED)
(1) General
• EJX/EJA-E Series pressure transmitters are
categorized as piping under the pressure
accessories section of directive 97/23/EC,
which corresponds to Article 3, Paragraph 3 of
PED, denoted as Sound Engineering Practice
(SEP).
• EJX110A-MS, EJX110A-HS,
EJX110A-VS, EJ130, EJ440, and
EJA110E with /HG can be used above 200
bar and therefore considered as a part of a
pressure retaining vessel where category III,
Module H applies. These models with option
code /PE3 conform to that category.
(2) Technical Data
• Models without /PE3
Article 3, Paragraph 3 of PED, denoted as
Sound Engineering Practice (SEP).
• Models with /PE3
Module: H
Type of Equipment: Pressure Accessory-Vessel
Type of fluid: Liquid and Gas
Group of fluid: 1 and 2
Model
Capsule
code
PS*
1
(bar)
V(L)
PS.V
(bar.L)
Category*
2
EJA110E
M, H, V
160
0.01
1.6
Article 3,
Paragraph 3
(SEP)
EJ110
F, L
EJX110A
M, H, V
250
0.01
2.5
EJA110E
with code
/HG
EJ110
with code
/PE3
M, H, V
250
0.01
2.5
III
EJ130
M, H
500
0.01
5.0
Article 3,
Paragraph 3
(SEP)
EJ130
with code
/PE3
M, H
500
0.01
5.0
III
EJ310 L, M, A, B
160
0.01
1.6
Article 3,
Paragraph 3
(SEP)
EJ430
H, A, B
160
0.01
1.6
Article 3,
Paragraph 3
(SEP)
EJ440
C, D
500
0.1
5.0
Article 3,
Paragraph 3
(SEP)
EJ440
with code
/PE3
C, D
500
0.1
5.0
III
*1: PS is maximum pressure for vessel itself based on
Pressure Equipment Directive 97/23/EC. Refer to
General Specification for maximum working pressure of a
transmitter.
*2: Referred to Table 1 covered by ANNEX II of EC Directive
on Pressure Equipment Directive 97/23/EC
(3) Operation
CAUTION
• The temperature and pressure of fluid should
be maintained at levels that are consistent
with normal operating conditions.
• The ambient temperature should be
maintained at a level that is consistent with
normal operating conditions.
• Please take care to prevent water hammer
and the like from inducing excessive
pressures in pipes and valves. If phenomena
are likely, install a safety valve or take
some other appropriate measure to prevent
pressure from exceeding PS.
• Take appropriate measures at the device or
system level to protect transmitters if they
are to be operated near an external heat
source.
2.12 Low Voltage Directive
Applicable standard: EN61010-1
(1) Pollution Degree 2
"Pollution degree" describes the degree to
which a solid, liquid, or gas which deteriorates
dielectric strength or surface resistivity is
adhering. " 2 " applies to normal indoor
atmosphere. Normally, only non-conductive
pollution occurs. Occasionally, however,
temporary conductivity caused by condensation
must be expected.
(2) Installation Category I
"Overvoltage category (Installation category)"
describes a number which defines a transient
overvoltage condition. It implies the regulation
for impulse withstand voltage. " I " applies to
electrical equipment which is supplied from the
circuit when appropriate transient overvoltage
control means (interfaces) are provided.