15) test output setup (k10: output x%), 16) user memo fields (m: memo), Span adjustment value (%) = p – Yokogawa EJA220A User Manual
Page 47: Ϫ a40 p
IM 01C21C01-01E
8-15
8. BRAIN TERMINAL BT200 OPERATION
Span adjustment value (%) =
P
1
: Actual differential pressure/pressure value
A40: Input (indicated as the value after zeroing)
Measurement pressure
Applied pressure
P
1
Ϫ A40
P
1
ϫ
100
A40
P
1
0
F0846.EPS
• Example: For the range of 0 to 30 kPa.
A40: INPUT = 30.15 kPa
J15: SPAN ADJ = 0.15 %
Suppose that a standard pressure of 30 kPa is applied and
the value of the parameter of A40: INPUT is 30.15 kPa.
Firstly, obtain the slope error for the span as follows;
Add
Ϫ0.5% to 0.15% of the current value to calculate the
accumulated span adjustment value.
0.15
ϩ (Ϫ0.50) = Ϫ0.35
F0847.EPS
FEED
NO
OK
SET
J15:SPAN ADJ
-0.35 %
ESC
CLR
DEL
SET
J15:SPAN ADJ
0.15 %
- 0.35
Set
Ϫ0.35.
Press key twice.
Press the (OK) key.
30.00
Ϫ30.15
30.00
ϫ 100 = Ϫ0.5 (%)
ϭ
Span adjustment value (%) =
Note: Enter 0.00 to J15: SPAN ADJ to reset the
span adjustment to the initial value at the
shipment.
P
1
Ϫ
A40
P
1
ϫ100
(15)
Test Output Setup (K10: OUTPUT X%)
This feature can be used to output a fixed current from
3.2 mA (–5%) to 21.6 mA (110%) for loop checks.
• Example: Output 12 mA (50%) fixed current.
ESC
SET
K10:OUTPUT X %
50.0 % ACTIVE
FEED
NO
OK
SET
K10:OUTPUT X %
0.0 %
+ 050.0
Set 50.0%.
Press the key twice to
output a fixed current at 50%.
“Active” is displayed while this is
being executed.
Press the (OK) key to cancel
the fixed current output.
F0834.EPS
IMPORTANT
1. Test output is held for approximately 10
minutes, and then released automatically after
the time has elapsed. Even if the BT200 power
supply is turned off or the communication cable
is disconnected during test output, it is held for
approximately 10 minutes.
2. Press the
(OK) key to release test output
immediately.
(16)
User Memo Fields (M: MEMO)
This feature provides 5 user memo fields, each holding
up to 8 alphanumeric characters. Up to 5 items such as
inspection date, inspector, and other information can be
saved in these fields.
• Example: Save an inspection date of January
30, 1995.
DATA
DIAG
PRNT
ESC
SET
M10:MEMO 1
95.1.30_
ESC
PARAM
M10:MEMO 1
M20:MEMO 2
M30:MEMO 3
Set 95.1.30 in the order of year,
month, and day.
Press the key twice to
enter the setting.
F0835.EPS