Page 21: Setup menu operation menu, Parameter value range factory default, Parameter value range factory default appears if

background image

Parameter

Value

Range

Factory Default

[`Pb1]

If

[`dFL]

is set to

[``US]

:

0 - 999°F/0 - 555°C/0 - 999 Units

25°F

0 - 99.9°F/0 - 55.5°C/0 - 99.9 Units

2.5°F

0 is set to ON/OFF control.

[`HSC]

is set to switch diff.

If

[`dFL]

is set to

[``SI]

:

0.0 to 999.9% of span

3%

[`rE1]

0.00 to 9.99 repeats/minute

0.00 repeats/minute

0.00 = No Reset. Won't appear if

[`Pb1]

is set to 0

or

[`dFL]

is set to

[``SI]

.

[`It1]

0.0 - 99.9 minutes/rpt. 0.00 = No Integral.

00.0 minutes/repeat

Won't appear if

[`Pb1]

is set to 0 or

[`dFL]

is set to

[``US]

.

[`rA1]

0.00 to 9.99 minutes

0.00 minutes

0.00 = No Rate. Will not appear if

[`Pb1]

is set to 0

or

[`dFL]

is set to

[``SI]

.

[`dE1]

0.00 - 9.99 minutes. 0.00 = No Derivative.

0.00 minutes

Won't appear if

[`Pb1]

is set to 0 or

[`dFL]

is set to

[``US]

.

[`Ct1]

0.1 to 999.9

5.0 seconds

Won't appear if

[`Pb1]

= 0, or

[`420]

.

[`Pb2]

Same as

[`Pb1]

.

[`Pb2]

lower limit = 1, 0.1, 0.01

[`rE2]

Same range as

[`rE1]

.

[`It2]

Same range as

[`It1]

.

[`rA2]

Same range as

[`rA1]

.

[`dE2]

Same range as

[`dE1]

.

[`Ct2]

Same range as

[`Ct1]

.

[`ALO]

Deviation

[``dE]

-999 to 0

-999

Process

[``Pr]

[``rL]

to

[`AHI]

[``rL]

Will not appear if

[`Ot2]

is set to

[``no]

or

[`Con]

.

[`AHI]

Deviation

[``dE]

0 to 999

999

Process

[``Pr]

[`ALO]

to

[``rH]

[``rH]

Will not appear if

[`Ot2]

is set to

[``no]

or

[`Con]

.

[`CAL]

±180°F/±100°C/±180 Units

0

[`AUt]

0-3

0

Series V4 Software Map

Parameter

Value

Range

Factory Default

Appears If:

[`LOC]

[```0]

,

[```1]

,

[```2]

,

[```3]

,

[```4]

**

0

[``In]

[```J]

,

[```H]

,

[```t]

,

[```n]

,

[```J]

DIP switch selectable.

[```S]

,

[`rtd]

,

[`r†d]

,

[`0-5]

,

[`420]

[`dEC]

0, 0.0, 0.00

0

[``In]

is set to

[`0-5]

or

[`420]

[`C_F]

[```C]

or

[```F]

Dependent on

[`dFL]

[``In]

is set to

[```J]

,

[```H]

,

[```t]

,

[```n]

,

[```S]

,

[`rtd]

, or

[`r†d]

[``rL]

[``rL]

to

[``rh]

Input dependent.

[``rh]

[``rh]

to

[``rL]

Input dependent.

[`Ot1]

[``ht]

or

[``CL]

[``ht]

[`HSC]

1 - 99, 0.1 - 9.9, 0.01 - 0.99°F

3, 0.3, 0.03°F

1 to 55, 0.1 to 5.5, 0.01 to 0.55°C

2, 0.2, 0.02°C

[`Ot2]

[`Con]

= Control

[`Con]

[`PrA]

= Process Alarm

[``Pr]

= Process with no alarm message

[`dEA]

= Deviation alarm

[``dE]

= Deviation with no alarm message

[``no]

= None

[`HSA]

1 - 9999, 0.1 - 999.9, 0.01 - 99.99°F

3, 0.3, 0.03°F

[`Ot2]

is not set to

[`Con]

1 - 5555, 0.1 - 555.5, 0.01 - 55.55°C

2, 0.2, 0.02°C

or

[``no]

[`LAt]

[`LAt]

or

[`nLA]

[`nLA]

[`Ot2]

is not set to

[`Con]

or

[``no]

[`SIL]

[``On]

or

[`OFF]

[`OFF]

[`Ot2]

is set to

[`dEA]

or

[``dE]

[`rtd]

[`JIS]

or

[`din]

[`din]

[``In]

is set to

[`rtd]

or

[`r†d]

[`rP`]

[`Str]

is set to Ramping on power up

[`OFF]

[``on]

is set to Ramping to set point always

[`OFF]

is set to None

[`rt`]

0 to 9999

100°/hr

[``rP]

is not set to

[`OFF]

[`P`L]

0 to 100

100

[`dsP]

[`nor]

= normal

[`nor]

[`SEt]

= Set Point (lower only)

[`Pro]

= Process (upper only)

Setup Menu

Operation Menu

V4

1
2
%

Enter the Setup Menu by
pressing the ¿Up-arrow
and ¯Down-arrow keys si-
multaneously for three sec-
onds. The lower display
shows the [`LOC] Lock
parameter, and the upper
display shows its current
level. All keys are inactive
until you release both keys.
You can reach the Lock
parameter from anywhere.
Use the ‰Advance key to
move through the menus
and the ¿Up-arrow and
¯Down-arrow keys to select
data. You will not see all
parameters in this menu,
depending on the con-
troller's configuration and
model number.

Note:
Do not enter any values
here; make photocopies
instead.

V4

1
2
%

**LOC Functions

[```0]

: All operating parameters may be viewed or changed. Manual operation is permitted. Bumpless transfer to manual

mode will occur on sensor break.

[```1]

: The set point, actual, and alarm settings are only visible parameters, set point is adjustable in this level. Manual

operation and auto-tune are permitted. Bumpless transfer to manual mode will occur on sensor break.

[```2]

: The set point, actual, and alarm settings are the only visible parameters, set point is adjustable in this level. Manual

operation is permitted. Bumpless transfer to manual mode will occur on sensor break.

[```3]

: The set point and actual are the only visible parameters, set point is adjustable in this level. Manual operation is not

permitted. Bumpless transfer is defeated and outputs are disabled on sensor break.

[```4]

: The set point and actual are the only visible parameters, set point is not adjustable in this level. Manual operation is

not permitted. Bumpless transfer is defeated and outputs are disabled on sensor break.