Specifications

(1465)

Control Mode
• Microprocessor-based, user selectable control

modes

• Single input, dual output
• 2.5Hz input sampling rate
• 1Hz display update rate
• Ramp to set point: 0 to 9999 degrees or units per

hour

• Heat and cool auto-tune operator interface
Operator Interface
• Sealed membrane front panel
• Dual, four-digit red or green displays

Advance,

¿

Up-arrow,

¯

Down-arrow, and

ˆ

Infinity keys

• User selectable screen display
Accuracy
• Calibration accuracy and sensor conformity: ±0.1%

of span, ±1°C @ 77°F ± 5°F (25°C ± 3°C) ambient
and rated line voltage

• Accuracy span: 1000°F (540°C) minimum
• Temperature stability: ±0.2°F/°F (±0.2°C/°C) rise in

ambient maximum

Sensors/Inputs
• Thermocouple, grounded or ungrounded sensors
• RTD 2- or 3-wire, platinum, 100

@ 0°C calibration

to DIN curve (0.00385

/

/°C) or JIS curve

(0.003916

/

/°C); user selectable

• Process, 4-20mA @ 5

, or 0-5V

Î

(dc) @ 10k

input impedance

• Sensor break protection de-energizes control output

to protect system or selectable bumpless transfer to
manual operation

• °F or °C or process units display, user selectable
Input Range

Specified temperature ranges represent the
controller’s operational span.

• Thermocouple

Type J

32 to 1382°F

or

0

to

750°C

Type K

-328 to 2282°F

or

-200

to 1250°C

Type N

32 to 2282°F

or

0

to 1250°C

Type S

32 to 2642°F

or

0

to 1450°C

Type T

-328 to

662°F

or

-200

to

350°C

• RTD Resolution (DIN or JIS)

-328 to 1292°F

or

-200

to

700°C

0.1°

-199.9 to 999.9°F

or -128.8

to 537.7°C

• Process

4-20mA @ 5

or

-999 to 9999 units

0-5V (dc) @ 10k

or

-999 to 9999 units

Output 1 (Heating or Cooling)
• Electromechanical relay1. Form C, rated at 8A @

125V~ (ac) or 5A @ 240V~ (ac) or 5A @ 30V

Î

(dc),

max. at resistive load, without contact suppression.
Max. switching current is 10A, max. switching power
is 2500VA, and max. switching voltage is 277V~
(ac) or 110V

Î

(dc).

• Switched dc signal provides a non-isolated minimum

turn on voltage of 3V

Î

(dc) into a minimum 500

load; maximum on voltage not greater than 12V

Î

(dc) into an infinite load.

• 4-20mA reverse or direct acting, non-isolated 0 to

800

load.

• Solid-state relay3, Form A, 0.5A @ 24V~ (ac) min.,

264V~ (ac) max., opto-isolated burst fire switched,
without contact suppression. Off-state output
impedance is 31M

.

Output 2 (Heat, Cool or Alarm)
• Electromechanical relay1. Form C, rated at 8A @

125V~ (ac) or 5A @ 240V~ (ac) or 5A @ 30V

Î

(dc),

max. at resistive load, without contact suppression.
Max. switching current is 10A, max. switching power
is 2500VA, and max. switching voltage is 277V~
(ac) or 110V

Î

(dc).

• Switched dc signal provides a non-isolated minimum

turn on voltage of 3V

Î

(dc) into a minimum 500

load; maximum on voltage not greater than 12V

Î

(dc) into an infinite load.

• Solid-state relay3, Form A, 0.5A @ 24V~ (ac) min.,

264V~ (ac) max., opto-isolated burst fire switched,
without contact suppression. Off-state output
impedance is 31M

.

• Alarm output can be latching or non-latching, and

process or deviation with separate high and low
values. Alarm silencing (inhibit) on power up (for
deviation alarms only).

Output Configurations
• Output 1
User selectable as: on/off: P, PI, PD, PID, heat or cool
action
• Adjustable switching differential: 1 to 99°F (1 to

55°C)

• Proportional band: 0 (off) or 1 to 999°F (0 to 555°C)

or 0.0 to 999.9 units

Integral: 0 (off) or 0.1 to 99.9 minutes per repeat
Reset: 0 (off) or 0.01 to 9.99 repeats per minute
Rate/derivative: 0 (off) or 0.01 to 9.99 minutes
Cycle time: 0.1 to 999.9 seconds
• Output 2
User selectable as: Control with action opposite that of
Output 1 (heating or cooling)
• Process or deviation alarm with flashing alarm

message

• Process or deviation alarm without alarm message
• Alarm with separate high and low set points
• Hysteresis: 1 to 9999° or units switching differential
Line Voltage/Power
• 100-240V~ (ac), -15%, +10%; (85-264V~ [ac])

50/60Hz, ±5%

• 14-24V

ı

(ac/dc), +10%, -15%; (12-26V

ı

[ac/dc])

50/60Hz, ±5%

• Fused internally (factory replaceable only) Slo-Blo®

type (time-lag):
1A, 250V for high voltage versions
2A, 250V for low voltage versions

• Maximum power consumption: 12VA (100 to 240V~

[ac]), 7VA (12 to 24V

ı

[ac/dc])

• Data retention upon power failure via non-volatile

memory