Output 2 Wiring

Figure 11a –

Mechanical Relay Without Contact Suppression

V4T _ - _ D _ _ - _ _ _ _
Form C, rated at 8A @ 125V~ (ac) or 5A @ 240V~ (ac). Minimum load current: 100mA @ 5VÎ (dc)

Figure 11b –

Solid State Relay Without Contact Suppression

V4T _ - _ K _ _ - _ _ _ _
0.5 amps (AC loads only)

18

17

16

15

14

13

Customer Supplied

Quencharc

SS2

SS2

L2

L1

Fuse

External

Load

4

5

6

18

17

16

15

14

13

8

7

OFF

1 2

18

17

16

15

14

13

L1

L2

COM

NC
NO

External

Load

Fuse

Customer

Supplied

Quencharc

4

5

6

18

17

16

15

14

13

8

7

OFF

1 2

Indication

Probable Cause(s)

P o w e r

• No power.

• Power to unit may be off.
• Fuse may be blown.
• Breaker may be tripped.
• Safety interlock door switch etc. may be activated.
• Separate system limit control may be latched.
• Wiring may be open.
• Input Power may be incorrect.

Alarms •

Alarm won’t occur.

• Alarm output may be off.
• Alarm set points may be incorrect.
• Alarm may be silenced.
• Alarm sides may be incorrect.
• Controller may be in diagnostics mode.

• Alarm won’t clear.

• Alarm may be latched.
• Alarm set points may be incorrect.
• Alarm hysteresis may be incorrect.
• Input may be in error condition.

Error Code Messages (

[----] in the upper display indicates a Series V4 error; error code number is visible in bottom display)

• [----] [ Er2]

• Sensor underrange error (applies only to RTD units)

• [----] [`Er4]

• Configuration error.

• [----] [`Er5]

• Non-volatile checksum error

• [----] [`Er6]

• A/D underflow error.

• [----] [`Er7]

• A/D overflow error.

Troubleshooting Alarms and Errors