Output 2 wiring, Switched dc, open collector, Figure 12a – Watlow Series V4 User Manual

Page 12: External load

background image

Corrective Action

• Check switches, fuses, breakers, interlocks, limits, connectors,

etc. for energized condition and proper connection.

• Measure power upstream for required level. Check part number for input power required.
• Check wire size.
• Check for bad connections.
• Configure output as an alarm.

Check alarm set points..

• To clear the alarm, correct the alarm condition; check to see if the alarm is latched.
• Check the alarm sides setting.
• Check the alarm type setting.
• Check the alarm logic for compatibility with system peripherals and annunciators.
• Check the power limit setting.
• Check the operation mode.
• Check the alarm output function.
• Check the °C or°F setting.
• Check the calibration offset value; set it to a lower level.

)

• Sensor input generated a value lower than allowable signal range, or A/D circuitry malfunctioned. Enter a valid

input. Make sure [``In] parameter (Setup Menu) matches your sensor and DIP switches are set accordingly.

• Microprocessor is faulty; consult factory.
• Unless power interruption occurred while controller was storing data, nonvolatile memory is bad; consult factory.
• A/D circuit is underrange. Check sensor; if functioning properly, consult factory. Make sure [``In] parameter

(Setup Menu) matches your sensor and DIP switches are set accordingly.

• A/D circuit is overrange. Check sensor; if functioning properly, consult factory. Make sure [``In] parameter

(Setup Menu) matches your sensor and DIP switches are set accordingly.

Output 2 Wiring

Figure 12a –

Switched DC, Open Collector

V4T _ - _ C _ _ - _ _ _ _

13

unregulated

V+

V—

15

Internal Circuitry

4

5

6

18

17

16

15

14

13

8

7

18

17

16

15

14

13

External

Load

-

+

1 2

OFF

1 2