Wa t l o w S e r i e s S D C a l i b r a t i o n

7

F a c t o r y a n d C a l i b r a t i o n

Process Output Procedures

Equipment

Precision volt/ammeter with 3.5-digit resolution.

Output 1 Setup and Calibration

1.

Connect the correct power supply to terminals 1
and 2 (see Chapter Two).

Volts

2.

Connect the volt/ammeter to terminals 7 (-) and 6 (+).

3.

At Output 1 Calibrate, 1V

[01;1u] select [~YES]

and press the Advance Key

‰. The voltage output

value appears in the upper display. Press the Up

¿

or Down Key

¯ to adjust the upper display value

to match the value from the volt/ammeter. The unit
should stabilize within one second. Repeat until the
volt/ammeter reads 1.00V, ±0.1V. Press the Advance
Key

‰ to store the value and move to the next

prompt.

4.

At Output 1 Calibrate, 9V

[01;9u] select [~YES]

and press the Advance Key

‰. The voltage output

value appears in the upper display. Press the Up

¿

or Down Key

¯ to adjust the upper display value

to match the value from the volt/ammeter. The unit
should stabilize within one second. Repeat until the
volt/ammeter reads 9.00V, ±0.1V. Press the Advance
Key

‰ to store the value and move to the next

prompt.

5.

Rewire for operation and verify calibration.

Milliamperes

6.

Connect the volt/ammeter to terminals 7 (-) and 5
(+).

7.

At Output 1 Calibrate, 4 mA

[01;4a] select [~YES]

and press the Advance Key

‰. The current output

value appears in the upper display. Press the Up

¿

or Down Key

¯ to adjust the upper display value

to match the value from the volt/ammeter. The unit
should stabilize within one second. Repeat until the
volt/ammeter reads 4.00 mA, ±0.1mA. Press the
Advance Key

‰ to store the value and move to the

next prompt.

8.

At Output 1 Calibrate, 16 mA

[01;16] select [~YES]

and press the Advance Key

‰. The current output

value appears in the upper display. Press the Up

¿

or Down Key

¯ to adjust the upper display value

to match the value from the volt/ammeter. The unit
should stabilize within one second. Repeat until the
volt/ammeter reads 16.00 mA, ±0.1 mA. Press the
Advance Key

‰ to store the value and move to the

next prompt.

9.

Rewire for operation and verify calibration.

Output 3 Setup and Calibration

1.

Connect the correct power supply to terminals 1
and 2 (see Chapter Two).

Volts

2.

Connect the volt/ammeter to terminals 14 (-) and
13 (+).

3.

At Output 3 Calibrate, 1V

[03;1u] select [~YES]

and press the Advance Key

‰. The voltage output

value appears in the upper display. Press the Up

¿

or Down Key

¯ to adjust the upper display value

to match the value from the volt/ammeter. The unit
should stabilize within one second. Repeat until the
volt/ammeter reads 1.00V, ±0.1V. Press the Advance
Key

‰ to store the value and move to the next

prompt.

4.

At Output 3 Calibrate, 9V

[03;9u] select [~YES]

and press the Advance Key

‰. The voltage output

value appears in the upper display. Press the Up

¿

or Down Key

¯ to adjust the upper display value

to match the value from the volt/ammeter. The unit
should stabilize within one second. Repeat until the
volt/ammeter reads 9.00V, ±0.1V. Press the Advance
Key

‰ to store the value and move to the next

prompt.

5.

Rewire for operation and verify calibration.

Milliamperes

6.

Connect the volt/ammeter to terminals 14 (-) and
12 (+).

7.

At Output 3 Calibrate, 4 mA

[03;4a] select [~YES]

and press the Advance Key

‰. The current output

value appears in the upper display. Press the Up

¿

or Down Key

¯ to adjust the upper display value

to match the value from the volt/ammeter. The unit
should stabilize within one second. Repeat until the
volt/ammeter reads 4.00 mA, ±0.1mA. Press the
Advance Key

‰ to store the value and move to the

next prompt.

8.

At Output 3 Calibrate, 16 mA

[03;16] select [~YES]

and press the Advance Key

‰. The current output

value appears in the upper display. Press the Up

¿

or Down Key

¯ to adjust the upper display value

to match the value from the volt/ammeter. The unit
should stabilize within one second. Repeat until the
volt/ammeter reads 16.00 mA, ±0.1 mA. Press the
Advance Key

‰ to store the value and move to the

next prompt.

9.

Rewire for operation and verify calibration.

Restoring Factory Calibration

Press the Up

¿ and Down ¯ keys together for six

seconds until

[FaCT] appears in the upper display

and

[PagE] appears in the lower display.

Press the Advance Key

‰ to step through the pa-

rameters until the

[rESt] appears.

Use the Up Key

¿ to select [`yES] in the upper

display.

Press the Infinity Key

ˆ to exit the Factory Page.