Process output procedures, Output 1 setup and calibration, Output 3 setup and calibration – Watlow Series SD User Manual
Page 7: Restoring factory calibration
Wa t l o w S e r i e s S D C a l i b r a t i o n
■
7
■
F a c t o r y a n d C a l i b r a t i o n
Process Output Procedures
Equipment
•
Precision volt/ammeter with 3.5-digit resolution.
Output 1 Setup and Calibration
1.
Connect the correct power supply to terminals 1
and 2 (see Chapter Two).
Volts
2.
Connect the volt/ammeter to terminals 7 (-) and 6 (+).
3.
At Output 1 Calibrate, 1V
[01;1u] select [~YES]
and press the Advance Key
‰. The voltage output
value appears in the upper display. Press the Up
¿
or Down Key
¯ to adjust the upper display value
to match the value from the volt/ammeter. The unit
should stabilize within one second. Repeat until the
volt/ammeter reads 1.00V, ±0.1V. Press the Advance
Key
‰ to store the value and move to the next
prompt.
4.
At Output 1 Calibrate, 9V
[01;9u] select [~YES]
and press the Advance Key
‰. The voltage output
value appears in the upper display. Press the Up
¿
or Down Key
¯ to adjust the upper display value
to match the value from the volt/ammeter. The unit
should stabilize within one second. Repeat until the
volt/ammeter reads 9.00V, ±0.1V. Press the Advance
Key
‰ to store the value and move to the next
prompt.
5.
Rewire for operation and verify calibration.
Milliamperes
6.
Connect the volt/ammeter to terminals 7 (-) and 5
(+).
7.
At Output 1 Calibrate, 4 mA
[01;4a] select [~YES]
and press the Advance Key
‰. The current output
value appears in the upper display. Press the Up
¿
or Down Key
¯ to adjust the upper display value
to match the value from the volt/ammeter. The unit
should stabilize within one second. Repeat until the
volt/ammeter reads 4.00 mA, ±0.1mA. Press the
Advance Key
‰ to store the value and move to the
next prompt.
8.
At Output 1 Calibrate, 16 mA
[01;16] select [~YES]
and press the Advance Key
‰. The current output
value appears in the upper display. Press the Up
¿
or Down Key
¯ to adjust the upper display value
to match the value from the volt/ammeter. The unit
should stabilize within one second. Repeat until the
volt/ammeter reads 16.00 mA, ±0.1 mA. Press the
Advance Key
‰ to store the value and move to the
next prompt.
9.
Rewire for operation and verify calibration.
Output 3 Setup and Calibration
1.
Connect the correct power supply to terminals 1
and 2 (see Chapter Two).
Volts
2.
Connect the volt/ammeter to terminals 14 (-) and
13 (+).
3.
At Output 3 Calibrate, 1V
[03;1u] select [~YES]
and press the Advance Key
‰. The voltage output
value appears in the upper display. Press the Up
¿
or Down Key
¯ to adjust the upper display value
to match the value from the volt/ammeter. The unit
should stabilize within one second. Repeat until the
volt/ammeter reads 1.00V, ±0.1V. Press the Advance
Key
‰ to store the value and move to the next
prompt.
4.
At Output 3 Calibrate, 9V
[03;9u] select [~YES]
and press the Advance Key
‰. The voltage output
value appears in the upper display. Press the Up
¿
or Down Key
¯ to adjust the upper display value
to match the value from the volt/ammeter. The unit
should stabilize within one second. Repeat until the
volt/ammeter reads 9.00V, ±0.1V. Press the Advance
Key
‰ to store the value and move to the next
prompt.
5.
Rewire for operation and verify calibration.
Milliamperes
6.
Connect the volt/ammeter to terminals 14 (-) and
12 (+).
7.
At Output 3 Calibrate, 4 mA
[03;4a] select [~YES]
and press the Advance Key
‰. The current output
value appears in the upper display. Press the Up
¿
or Down Key
¯ to adjust the upper display value
to match the value from the volt/ammeter. The unit
should stabilize within one second. Repeat until the
volt/ammeter reads 4.00 mA, ±0.1mA. Press the
Advance Key
‰ to store the value and move to the
next prompt.
8.
At Output 3 Calibrate, 16 mA
[03;16] select [~YES]
and press the Advance Key
‰. The current output
value appears in the upper display. Press the Up
¿
or Down Key
¯ to adjust the upper display value
to match the value from the volt/ammeter. The unit
should stabilize within one second. Repeat until the
volt/ammeter reads 16.00 mA, ±0.1 mA. Press the
Advance Key
‰ to store the value and move to the
next prompt.
9.
Rewire for operation and verify calibration.
Restoring Factory Calibration
•
Press the Up
¿ and Down ¯ keys together for six
seconds until
[FaCT] appears in the upper display
and
[PagE] appears in the lower display.
•
Press the Advance Key
‰ to step through the pa-
rameters until the
[rESt] appears.
•
Use the Up Key
¿ to select [`yES] in the upper
display.
•
Press the Infinity Key
ˆ to exit the Factory Page.