beautypg.com

Calibrating the series sd, Thermocouple input procedure, Rtd input procedure – Watlow Series SD User Manual

Page 6: Voltage process input procedure, Current process input procedure

background image

Wa t l o w S e r i e s S D C a l i b r a t i o n

6

F a c t o r y a n d C a l i b r a t i o n

Calibrating the Series SD

Warm up the unit for 20 minutes. To reach the cali-

bration prompts, enter the Factory Page by holding
down the Up Key

¿ and Down Key ¯ for six seconds.

Once in the Factory Page

[FACT], use the Advance ‰

key to select a prompt. The last prompts on the Factory
Page are the input and output calibration prompts.

You can restore the original factory calibration with

Restore Factory Calibration

[rESt] (Factory Page).

*Note: INFOSENSE

TM

should be turned off while verifying calibration

of the controller with a calibration source.

Thermocouple Input Procedure

Equipment

Type J reference compensator with reference junc-
tion at 0°C (32°F), or type J thermocouple calibra-
tor to 0°C (32°F).

Precision millivolt source, 0 to 50 mV minimum
range, 0.002 mV resolution.

Input Setup and Calibration

1.

Connect the correct power supply to terminals 1
and 2 (see Chapter Two).

2.

Connect the millivolt source to terminals 11 (-) and
10 (+) with copper wire.

3.

Enter 50.00 mV from the millivolt source. Allow at
least 10 seconds to stabilize. Set Thermocouple Cal-
ibration, 50 mV

[tc;50] to [`yES]. Press the Ad-

vance Key

‰ to store 50.000 mV input and move to

the next prompt.

4.

Enter 0.000 mV from the millivolt source. Allow at
least 10 seconds to stabilize. Set Thermocouple Cal-
ibration, 0 mV

[tc;00] to [`yES]. Press the Ad-

vance Key

‰ to store 0.000 mV input and move to

the next prompt.

5.

Disconnect the millivolt source and connect the ref-
erence compensator or thermocouple calibrator to
terminals 11 (-) and 10 (+). With type J thermocou-
ple wire, if using a compensator, turn it on and
short the input wires. When using a type J calibra-
tor, set it to simulate 0°C (32°F). Allow 10 seconds
for the controller to stabilize. Set Thermocouple
Calibration, 32°

[tc;32] to [`yES]. Press the Ad-

vance Key

‰ to store type J thermocouple calibra-

tion and move to the next prompt.

6.

Rewire for operation and verify calibration.

RTD Input Procedure

Equipment

1 k

decade box with 0.01

resolution.

Input Setup and Calibration

1.

Connect the correct power supply to terminals 1
and 2 (see Chapter 2).

2.

Connect the decade box to terminals 10 (S1), 11
(S3) and 8 (S2), with 20 to 24-gauge wire.

3.

Enter 15.00

from the decade box. Allow at least

10 seconds to stabilize. Set RTD Calibration, 15

[`r;15] to [`yES]. Press the Advance Key ‰ to
store the 15.00

input and move to the next

prompt.

4.

Enter 380.00

from the decade box. Allow at least

10 seconds to stabilize. Set RTD Calibration, 380

[r;380] to [`yES]. Press the Advance Key ‰ to
store the 380.00

input and move to the next

prompt.

5.

Rewire for operation and verify calibration.

Voltage Process Input Procedure

Equipment

Precision voltage source, 0 to 10V minimum range,
with 0.001V resolution.

Input Setup and Calibration

1.

Connect the correct power supply to terminals 1
and 2 (see Chapter Two).

Input

2.

Connect the voltage source to terminals 11 (-) and
9 (+) of the controller.

3.

Enter 1.00V from the voltage source to the con-
troller. Allow at least 10 seconds to stabilize. Set In-
put Calibrate, 1V

[``u;1] to [`yES]. Press the Ad-

vance Key

‰ to store the 1.00V input and move to

the next prompt.

4.

Enter 9.00V from the voltage source to the con-
troller. Allow at least 10 seconds to stabilize. Set In-
put Calibrate, 9V

[``u;9] to [`yES]. Press the Ad-

vance Key

‰ to store the 9.00V input and move to

the next prompt.

5.

Rewire for operation and verify calibration.

Current Process Input Procedure

Equipment

Precision current source, 0 to 20 mA range, with
0.01 mA resolution.

Input Setup and Calibration

1.

Connect the correct power supply to terminals 1
and 2 (see Chapter Two).

2.

Connect the current source to terminals 11(-) and
8(+).

3.

Enter 4.00 mA from the current source to the con-
troller. Allow at least 10 seconds to stabilize. Set In-
put Calibrate, 4 mA

[``A;4] to [`yES]. Press the

Advance Key

‰ to store the 4 mA input and move

to the next prompt.

4.

Enter 16.00 mA from the current source to the con-
troller. Allow at least 10 seconds to stabilize. Set In-
put Calibrate, 16 mA

[`A;16] to [`yES]. Press the

Advance Key

‰ to store the 16 mA input and move

to the next prompt.

5.

Rewire for operation and verify calibration.