beautypg.com

Eia-485, Eia/tia-485 interface pinouts, Connecting the control and computer – Watlow Series 734 Data Communications User Manual

Page 6: Eia/tia-485 interface wiring, Connecting the control and the computer

background image

How to Use Data Communications

6

WATLOW Series 733/734

EIA-485

˜

NOTE:
The Electronic
Industry Associa-
tion EIA/TIA-485
standard recom-
mends a maximum
4000 ft. total net-
work distance.

Figure 3 -
EIA/TIA-485 Inter-
face, Pin Designa-
tions.

EIA/TIA-485 Interface Pinouts

73xx-xxxx-xDxx

The EIA/TIA-485 communications uses a two wire (half duplex) system. There are
only two lines, both lines used for transmitting and receiving. Only one device, the
computer or the control, can be speaking at a time. The Series 733/734 requires a
7 millisecond delay between transmission and receipt of data. With EIA/TIA-485
you can have from one to thirty-two Series 733/734 controls connected to a com-
puter.

This diagram is a typical wiring example. The connections on the host computer
may vary depending on models. See page 7 for information about serial interfaces.
Refer to your computer user's manual for more information.

Connecting the Control and the Computer

Remove power from both the Series 733/734 and your computer before connecting
them together. This prevents noise or static interference from entering the data
communication lines. Assemble a cable and the appropriate wiring at your com-
puter. Refer to the wiring on pages 4 through 6. As soon as you connect the data
communications lines, you may apply power to your system.

12

11

10

9

8

7

6

5

4

3

2

1

12

11

10

9

8

7

6

5

4

3

2

1

Twisted Pair Wire

Twisted Pair Wire

Common Pin 8

Common Pin 8

B

A

Gnd.

EIA/TIA-485

Interface

Series 733

#1

Series 733

#2

T+ / R+

T- / R-

Com

T+ / R+

T- / R-

Com

T+ / R+

T- / R-

Com

This manual is related to the following products: