background image

How to Use Data Communications

19

WATLOW Series 733/734

Name

Description

Read (?) and/or Write (=) Syntax

Range

(data.1)

Add ETX & STX with ANSI X3.28 Protocol

(data.2)

MDKY Mode Key Action

= MDKY 1

1 = One MODE Key press

MDL

Model Number

? MDL

x1 = 3 or 4; horiz. or vert. unit

Responds 73x-xx-x

x2 & x3 = Last two

(See Model # , p. 21)

characters of model #, AA-XX
x4 = Software rev; 0-9 or A-X

MENU Menu Step

? MENU menu

Data entered must be within

step

individual prompt guidelines,

= MENU menu

i.e., SP1 = R1L to R1H, etc.

step sp1 sp2

Enter data for sp2 and events

hours or minutes minutes or

even if they are not available.

seconds events

See 733/4 Program Manual.

MODE Mode Status

? MODE

0 = Operation mode
1 = Program mode
2 = Setup mode
3 = Service mode
4 = Calibration mode

MS

Melt Cycle

? MS

0 = Melt cycle OFF

= MS data.2

1 = Melt cycle ON

PB1

Zone 1 Prop Band

? PB1

0 to 999°F

= PB1 data.2

0 to 555°C

PB2

Zone 2 Prop Band

? PB2

0 to 999°F

= PB2 data.2

0 to 555°C
0 to 999 Units

RA1

Zone 1 Rate

? RA1

0 to 9.99 minutes

= RA1 data.2

RA2

Zone 2 Rate

? RA2

0 to 9.99 minutes

= RA2 data.2

RE1

Zone 1 Reset

? RE1

0 to 9.99 repeats per minute

= RE1 data.2

RE2

Zone 2 Reset

? RE2

0 to 9.99 repeats per minute

= RE2 data.2

RH1

Zone 1 Range High

? RH1

RL1 to max. INP1 type range

= RH1 data.2

RH2

Zone 2 Range High

? RH2

RL2 to max. INP2 type range

= RH2 data.2

RL1

Zone 1 Range Low

? RL1

Min. INP1 type range to RH1

= RL1 data.2

RL2

Zone 2 Range Low

? RL2

Min. INP2 type range to RH2

= RL2 data.2

RTD

RTD Curve

? RTD

0 = DIN

= RTD data.2

1 = JIS

RUN

Menu Run

= RUN menu

n = Run Menu n

SIL

Alarm Silence

? SIL

0 = OFF

= SIL data.2

1 = ON

STAT

Run Status

? STAT

x x; x1=0 idle or 1 run, x2=menu#

STP

Maximum Steps

? STP

1 = 1 Step

= STP data.2

2 = 2 Steps
3 = 3 Steps

STOP

Menu Stop

= STOP menu

n = Stop Menu n

TCMP Temperature

? TCMP

0 = OFF

Compensation

= TCMP data.2

1 = ON

TREM Time Remaining

? TREM

Learn Menu time remaining

TS

Time Select

? TS

0 = minutes : seconds

= TS data.2

1 = hours : minutes

Table 5 -
Command Summary
with Read (?) and
Write (=) Simple
Syntax and Data
Range/Responses.

Commands

This manual is related to the following products: