AnaWin3 Quickstart Guide

Installation

Doc.# 22852-10

Watlow Anafaze

9

WARNING!

Power is shut off to the PPC during the fol-
lowing procedure. Power cycling will inter-
fere with process control. Do not perform this
procedure if interrupting process control is
not acceptable.

1.

Close AnaWin and LogicPro if either is running.

2.

Connect only the PPC to be configured to the computer
on which AnaWin is installed.

3.

Set the rotary switch on the Processor Module to position

H

.

4.

Turn off power to the PPC system.

5.

Turn power on to the PPC system.

6.

Launch PPCComSu.

7.

Select the desired

'

for each port.

8.

Select the desired Modbus address for the PPC system.

9.

Click the

button.

10. Close PPCComSu.

11. Set the rotary switch on the Processor Module to position

D

.

12. Turn off power to the PPC system.

13. Turn on power to the PPC system.

Once configured with unique addresses, as many as 32 PPC
controllers may be connected to the PC on a 485 communica-