Setting programmable modbus addresses, Setting programmable modbus addresses 8 – Watlow ANAWIN 3 User Manual
Page 11

Installation
AnaWin3 Quickstart Guide
8
Watlow Anafaze
Doc.# 22852-10
You will also need this serial number any time you re-
quest technical support.
8.
Click
-or-
click
to abort the program.
A message box displaying
will appear. Click
to view the
screen.
9.
From the
menu on the
screen, se-
lect
, then the Com Port used to communicate with
the PPC-2000 controller.
10. For up to 4 controllers, click
to select each controller
address.
11. Click
.
For more than 4 controllers, see the AnaWin Help file
Adding Controllers to a System for more information on
communicating with your PPC-2000.
12. Click
. If the communications test result is
, verify the Com Port setting, controller address, and
connections. If the communications test result displays
the firmware version for each controller, communica-
tions are setup properly.
13. From the
!
menu, select
"
, then
.
14. On the Windows system task bar, click
, then
#
, then
, then
$
15. Select
%
from the
&
menu to verify that
AnaWin is communicating with each of the controllers.
Setting Programmable Modbus Addresses
Modbus addresses one through four may be set using the rota-
ry switch on the face of the PPC-2010 Processor Module. See
Setting Programmable Modbus Addresses on page 8 for infor-
mation on setting the rotary switch. The following procedure
describes how to set other addresses: