beautypg.com

Installations, Pl-3000b series installation – Proface APL3000B - Node Box PC User Manual

Page 14

background image

14

Installations

1.

PL-3000B Series Installation

Installation Requirements

• For easier maintenance, operation, and improved ventilation, be sure to install the PL at least

50mm [1.97 in.] away from adjacent structures and other equipment. 120 mm [4.72 in.] space
(minimum) is necessary at the front for cable curve.

• Be sure that the surrounding air temperature and the ambient humidity are within their specified

ranges.
Check the surrounding air temperature 30 mm [1.18 in.] away from the main unit.

• Be sure that heat from surrounding equipment does not cause the PL to exceed its standard

operating temperature.

Horizontal mounting

(Front)

50

[1.97]

50 [1.97]

50 [1.97]

Unit:mm[in.]

50 [1.97]

50

[1.97]

50

[1.97]

Horizontal mounting

(Right side)

50

[1.97]

50 [1.97]

120

[4.72]

Vertical mounting

(Front)

Vertical mounting

(Right side)

50

[1.97]

50

[1.97]

120

[4.72]

120

[4.72]

50 [1.97]

50 [1.97]

50

[1.97]

50[1.97]

50[1.97]

50

[1.97]

Wall mounting

(Front)

Wall mounting

(Left side)

Ex.: Horizontal mounting

30

[1.18]

30 [1.18]

30

[1.18]

Unit:mm[in.]

30

[1.18]

30 [1.18]

30

[1.18]