Programming functions: default settings – Warner Electric CBPC-3590 User Manual
Page 11
Warner Electric • 800-825-9050
P-291-1 • 819-0526 11
q
2. Re-tighten encoder bracket securely.
q
3 . Proceed to step 1 of the start-up procedure,
page 9 to recalibrate the system .
Note: If in doubt about encoder positioning, refer to
new encoder installation procedure, page 6.
If unit has problems such as “windmilling” program
default needed, do the following steps:
q
a. Press the RUN/PGM key on the keypad.
q
b. Enter 1, 0, 0, 0 and then press the down arrow
repeatedly until the end display reads: “t8.rdy”.
q
c. Press the arrow right button.
q
d. Press the RUN/PGM key.
q
e . Proceed to step 1 of the start-up procedure
on page 9 to recalibrate the system .
This completes the installation and set-up of the
CBPC-3590 control. Close and latch the control
securely .
As the controller has been designed as an improved
version of the CBC1500-AHFC with additional
features and improved performance and reliability,
programming of the various parameters should only
be accomplished by qualified personnel .
To Enter the programming mode, follow the steps
below:
Open the controller front cover for access to the
keypad/display. Press the RUN PGM key on the
keypad/display
Display will show LOC. 0
Then press 1, 0, 0, 0
Display will show LOC. 1000
This has now placed you in the programming mode
where various parameters can be changed by using
the down arrow key to increment through the various
parameters .
Programming Functions:
Default Settings
Default
Press
Display
Value
Function
↓
h xxx
--
Home Position
↓
bd. xx
--
Brake Distance, PPR
↓ bdAue . 3
3
Cycles Averaged
↓ cc. 0.5000
0.5000
Count Correction
↓
dP. oFF
oFF
Decimal Point
↓ FrSt. oN
oN
Front Panel Reset
↓ PLoc. oFF
oFF
Panel Lock
↓ CrEt. oFF
oFF
Count Retention
↓ ArSt. oN
oN
Auto Reset
↓ o1. 0.20
0.20
Start Signal, ms
↓ o2. 0.01
0.01
Early Warning, ms
↓ o3. 0.20
0.20
Stop Signal, ms
↓ o4. 0.10
0.10
Zero Speed, ms
↓ o5. 0.05
0.05
Zero Speed + delay 1, ms
↓ o6. 0.05
0.05
Zero Speed + delay 2, ms
↓ o8. LatCH
LatCH
Batch Auto Reset
↓ d1. 0.10
0.10
Delay 1, ms
↓ d2. 0.01
0.01
Delay 2, ms
↓ 05P .25
.25
Zero Speed Window, sec
↓ 5 -.-.-.-.-.-. -.-.-.-.-.-.
Start Release
↓ L - .- .- .- .- .- . - .- .- .- .- .- .
Move Preset Release
↓ E - .- .- .- .- .- . - .- .- .- .- .- .
Early Warning Release
↓ r - .- .- .- .- .- . - .- .- .- .- .- .
Reset Release
↓ bd. OFF
OFF
Baud Rate
↓ Par. None
None
Parity
↓
PFr. 80
80
Output Frequency, Hz.
↓
cPr. 90
90
Clutch Output Percentage
↓
bPr. 75
75
Brake Output Percentage
↓
JPr. 40
40
Jog Output Percentage
↓
cBt 15
15
Clutch Boost Percentage **
↓
bBt 40
40
Brake Boost Percentage **
↓ Id.no. xxx
xxx
Unit Number (Up to 3 digits)
↓
t0. rdy
rdy
Keyboard test
↓
t1 . rdy
rdy
RAM test
↓
t2 . rdy
rdy
Inputs test
↓
t3 . rdy
rdy
Outputs test
↓
t4 . rdy
rdy
Display test
↓
t5. rdy
rdy
Memory test
↓
t6. rdy
rdy
Date Code
↓
t7 . rdy
rdy
Serial Test
↓
t8. rdy
rdy
Reset Default Program
** Only when the OEX add-on board is installed in the CBPC-3590 are